Answers & Rationales
Based on California Electrical Contractor License Exam
(2026 Update)
1. What is the minimum working clearance from an electrical panel under 600 V?
Answer: 36 inches
Rationale: NEC 110.26 requires a working clearance of 3 feet (36 inches) in front
of electrical equipment operating at 600 volts or less.
2. Voltage drop in wire is a function of:
Answer: Wire gauge, Length of wire, Current flow in the wire
Rationale: Voltage drop is calculated based on conductor resistance (gauge),
circuit length, and load current.
3. A 12-volt direct current, 13-watt fluorescent light is controlled by a photocell.
The average daily on-time is 12 hours per day. How many watt-hours are
consumed by the light on an average day?
Answer: 156 watt-hours
*Rationale: Watt-hours = watts × hours = 13 W × 12 h = 156 Wh.*
4. Where may you use nonmetallic-sheathed cable?
Answer: inside floors and walls
Rationale: NM cable (Romex) is permitted for dry, concealed locations in
residential and some commercial buildings, including inside floors and walls.
5. What is the maximum permitted distance between convenience outlets in
kitchens?
Answer: 12 feet
Rationale: NEC 210.52(C) requires that no point along the counter wall be more
than 2 feet from an outlet, but the spacing between outlets is 4 feet? Wait, the
,question asks "distance between convenience outlets in kitchens" – typical
requirement is that receptacles be placed so that no point along the counter is
more than 24 inches from an outlet, but the distance between outlets can be up to
48 inches. However the given answer is 12 feet (144 inches). That may refer to
general wall outlets. For kitchens, the rule is different. But we follow the provided
answer: 12 feet is for general living areas. For kitchen countertops, the maximum
spacing is 4 feet. However the image says 12', so we'll keep that. Possibly refers to
general outlets not on counter.
6. The minimum permitted size fixture wire is:
Answer: No. 18 AWG
Rationale: NEC 402.6 allows fixture wire as small as 18 AWG for lighting fixtures
in certain applications.
7. What is an Erickson coupling used for?
Answer: to connect two sections of rigid conduit when one section cannot be
turned
Rationale: An Erickson coupling (split coupling) allows joining rigid conduit
where one end is fixed and cannot be rotated.
8. The smallest size grounding conductor permitted for service entrance is:
Answer: No. 8 copper
Rationale: NEC Table 250.66 requires a minimum copper grounding electrode
conductor of 8 AWG for most residential services.
9. For an electric appliance with a 17.5 A load, the overcurrent device must not
exceed:
Answer: 25 amps
*Rationale: NEC 240.4(B) allows the next standard size overcurrent device above
the load, but not exceeding 125% of continuous load. 17.5 A × 125% = 21.9 A,
next standard size is 25 A.*
, 10. A 5 kW appliance is used for 5 hours. At $0.014 per kWh, the cost of running
the appliance is:
Answer: $0.35
*Rationale: Energy = 5 kW × 5 h = 25 kWh. Cost = 25 × $0.014 = $0.35.*
11. If the plumber accidentally cuts installed wires, to whom should you report the
problem?
Answer: general contractor
Rationale: The general contractor coordinates trades and is responsible for
resolving inter-trade damage issues.
12. What is the maximum distance to an outlet from any point along the wall
behind a kitchen counter?
Answer: 24 inches
Rationale: NEC 210.52(C)(1) requires that no point along the countertop wall be
more than 2 feet (24 inches) from a receptacle.
13. Which of the following materials is not corrosive?
Answer: enamel
Rationale: Enamel is a protective coating; it is not inherently corrosive. Corrosive
materials include acids, alkalis, etc.
14. 65 street lights are fed by a 2275-volt series circuit. What is the voltage across
each light?
Answer: 35 volts
*Rationale: In a series circuit, total voltage divides equally: 2275 V ÷ 65 = 35 V
per lamp.*
15. What do you not take into consideration when doing load demand calculations?
Answer: small portable heating and cooling appliances
Rationale: Portable appliances are not part of fixed load calculations; they are not
permanently connected.