what is the maximum distance between supports on a vertical raceway? - Correct Answers15 feet
what must be installed every 100 feet in a vertical raceway? - Correct Answersstrain supports
what switch is installed in areas of the country subject to earthquake is imminent? - Correct Answersa
seismic switch
what is the minimum overhead clearance for raceways mounted in the machine room overhead? -
Correct Answers7 feet
what is the maximum length of motor-generator leads that may be connected directly to the controller
without being run inside a raceway? - Correct Answers6 feet
you have a 10' length of 3/4" rigid conduit which needs to have a 90* bend with a 16" stub height. with
a 7" take-up, what is the distance from the end of the pipe to the mark where the hickey arrow is
aligned? - Correct Answers9 inches
when a vertical raceway exceeds 100 feet, what precaution must be taken? - Correct Answersallow 1/4"
gap between sections
what hazard is present in a class 1 location? - Correct Answersflammable gasses
what purpose does a fish tape serve? - Correct Answersit is used to pull wires in conduit
how many threads per inch are there on a 10-24 machine screw? - Correct Answers24