what does HMIS stand for - ANSWERS-Hazardous Material
Identificaion System
what classification of fires requires a rating number behind the
classification letter - ANSWERS-A&B
required building protection - ANSWERS-requires F.E. for class A fires
occupation Hazard protection - ANSWERS-requires classified F.E.'s for
the potential fires present
installation height for a F.E weighing OVER 40lbs - ANSWERS-the top
shall not exceed 3 1/2 ft
installation height for a FE weighing 40lbs or LESS - ANSWERS-the
top shall not exceed 5 ft
MINIMUM installation height for any FE - ANSWERS-the bottom shall
not be lower than 4 inches
maximum travel distances to FE for each classification - ANSWERS-A-
75ft
END OF
PAGE 1
, TFM02 TEST LATEST
B-50
C-not specified
D-75
K-30
what type of FE's have the potential to be non rechargeable? -
ANSWERS-Dry chemical and halon agent
maintenance procedures shall include an examination of - ANSWERS--
mechanical parts
-extinguishing agent
-expelling means
-physical condition
what type of FE requires all agent be removed if partial has been
removed? - ANSWERS-water mistor wet chemical
all extinguishers besides ________ requires a verification of service
collar after being recharged - ANSWERS-Cartridge- or cylinder-
operated
END OF
PAGE 2