_______ _____________ _______________, when not specified, shall
be tested to factory test pressure, not exceeding 3 times the service
pressure. - ANSWERS-Low Pressure Cylinder
What is tested at original factory pressure? - ANSWERS-Cartridge
operated extinguishers
Which high pressure cylinders are tested at 5/3 service pressure? -
ANSWERS-DOT3A, 3AA, and 3AL
CO2 extinguishers with ICC3 specs are tested at ________________
psi. - ANSWERS-3,000
What psi level are CO2 hose assemblies tested at? - ANSWERS-1250
psi
What is tested at 300 psi or service pressure whichever is higher? -
ANSWERS-dry chemical, powder, water, foam, and halogen hose
assemblies
What is the psi test level for low pressure accessory hose on wheeled
extinguishers? - ANSWERS-300 psi
END OF
PAGE
1
, TFM02 EXAM LATEST
What is the psi test level for high pressure accessory hose on wheeled
extinguishers? - ANSWERS-3,000 psi
Hose assemblies that pass the hydrostatic test shall not require
____________ or _____________. correct answerrecording labeling or
marking ____________ ________________ assumes role of authority
having jurisdiction. - ANSWERS-property owner
Class A hazard has a travel distance from ______ ________ to
______________. - ANSWERS-any point to extinguisher
Class _____, ______, _____ hazards have a travel distance is from the
hazard to the extinguisher - ANSWERS-B, D, K
What does HMIS stand for? - ANSWERS-Hazardous Material
Identification System
What is the minimum discharge duration for extinguishers rated at 2A or
higher? - ANSWERS-13 seconds
END OF
PAGE
2
, TFM02 EXAM LATEST
What are the class A hazard extinguishers? - ANSWERS-Water,
halogenated, multipurpose dry chemical, and wet chemical
What are the class B hazard extinguishers? - ANSWERS-AFFF, FFFP,
CO2, Dry Chemical, Halogenated
How do you calculate the class A hazard installation minimum number
of extinguishers? - ANSWERS-divide the total floor area by the
maximum area to be protected per extinguisher
When can a smaller extinguisher rated class B or C not be used? -
ANSWERS-if they don't meet minimum 1-A rating
T/F Up to 2 water type extinguishers with 1-A rating can be used to
fullfill the rating of one 2-A extinguisher. - ANSWERS-True
T/F Two 2 1/2- A extinguishers shall be permitted to fulfill the
requirements of one 4-A rated extinguisher. - ANSWERS-false
What are the characteristics of a light hazard fire? - ANSWERS-2-A,
3,000 ft, 11,250 f