TFM02 EXAM STUDY GUIDE | FREQUENTLY
TESTED QUESTIONS WITH CORRECT
ANSWERS | BRAND NEW!
How often do dry chem with stainless steel shells need to be
inspected - ✔✔✔ Correct Answer > every 5 years
Where pressure is not specified on the extinguisher nameplate,
the extinguisher shall be tested at the factory test pressure, not
to exceed ___________ the extinguisher service pressure. - ✔✔✔
Correct Answer > 3 times
Fire extinguishers installed specifically for the protec- tion of
cooking appliances that use combustible cooking me- dia (animal
or vegetable oils and fats) without a Class K rating shall be
__________ from service. - ✔✔✔ Correct Answer > removed
Where a hazard is protected by an automatic fire pro- tection
system, a placard shall be conspicuously placed near the
extinguisher that states that the fire protection system shall be
actuated prior to using the fire extinguisher. True or False? - ✔✔✔
Correct Answer > True
,Page 2 of 25
Fire extinguishers for the protection of delicate electronic
equipment shall be selected from types specifically listed and
labeled for - ✔✔✔ Correct Answer > Class C hazards, dry chem cannot
be used
What extinguishers shall be used for Areas Containing Oxidizers
- ✔✔✔ Correct Answer > ONLY water type extinguishers
If, at any time, a fire extinguisher shows evidence of
___________________________ to the extent as to indicate weakness,
it shall be condemned or hydrostati- cally retested - ✔✔✔ Correct
Answer > dents,
Mechanical injury,
Or corrosion
Nonrechargeable halon agent-type fire extinguishers that show
evidence of dents, mechanical injury, or corrosion to the extent
indicating weakness shall be removed from ser- vice, shall not
be discharged, and shall be __________________ to per- mit
recovery of the halon. - ✔✔✔ Correct Answer > returned to the
manufacturer, a fire equipment dealer, or a distributor
, Page 3 of 25
The pressure in a hydrostatic test of a cylinder shall be
maintained for a minimum of _____________, seconds - ✔✔✔ Correct
Answer > 30 seconds
All valves, internal parts, and hose assemblies shall be removed,
and the fire extinguisher shall be emptied before testing, clear of
any extinguishing agent. True or false? - ✔✔✔ Correct Answer > True
All tests shall be conducted using test fittings and adapters. True
or false? - ✔✔✔ Correct Answer > true
What shall be cause for rejection or retest? - ✔✔✔ Correct Answer >
drop in pressure of test gauge indicating a leak
The hydrostatic testing of HIGH PRESSURE cylinders and
cartridges shall be in accordance with the procedures of
____________ - ✔✔✔ Correct Answer > TC, DOT, and CGA C-1.
For hose test, Pressure shall be applied at a rate of rise such
that the test pressure is reached in____________. - ✔✔✔ Correct
Answer > 1 minute