What time shall be recorded during a main drain test? ✓ ✓
...... ANSWER ....... Time for pressure to return to normal
at the end of the test when closing the main drain valve
The minimum number of antifreeze samples to be tested?
✓ ✓ ...... ANSWER ....... 2
, Page 2 of 29
A building has 630 sprinklers, how many should be tested?
✓ ✓ ...... ANSWER ....... 7
Systems installed prior to Sept 30 2012, listed antifreeze
solutions are not required until Sept 30 _____. ✓ ✓ ......
ANSWER ....... 2022
The concentration of antifreeze solution is limited to _____ %
glycerin by volume. ✓ ✓ ...... ANSWER ....... 50
The concentration of antifreeze solution is limited to ____ %
propylene glycol ✓ ✓ ...... ANSWER ....... 40
Sprinklers installed prior to ____ shall be replaced. ✓ ✓ ......
ANSWER ....... 1920
Criteria to not be considered in selection of sprinklers to be
tested ✓ ✓ ...... ANSWER ....... Ease of access
When one sprinkler fails testing ____ % of represented
sprinklers must be replaced ✓ ✓ ...... ANSWER ....... 100
, Page 3 of 29
Devices that can be used to test antifreeze solutions? ✓ ✓
...... ANSWER ....... Refractometer
Hydrometer
I need some fake answers ✓ ✓ ...... ANSWER .......
Spectrometer
Manometer
The supply valve is not opened to full flow would cause
what? ✓ ✓ ...... ANSWER ....... A large drop in full flow
pressure to be observed during a main drain test
An obstruction in the system would cause what? ✓ ✓ ......
ANSWER ....... A large drop in full flow pressure to be
observed during a main drain test
The sole water source is through a backflow preventer, a
main drain test shall be conducted at what interval? ✓ ✓
...... ANSWER ....... Quarterly