SYSTEMS,
S12 Sprinkler Test Questions and Answers
1. THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND
TO DETER- MINE QUALIFICATIONS.
Answer OWNER
2. RECORDS OF ALL INSPECTIONS AND MX
SHALL BE MAINTAINED ON PREMIS- ES FOR A MIN. OF YEARS.
Answer 3
3. THE BUILDING
OWNER SHALL ASSIGN A(N) TO COMPLY
WITH REQUIREMENTS.
Answer IMPAIRMENT COORDINATOR
4. REG
ULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.
Answer 1
5. SHUTDOWNS AFFECTING
,MORE THAN FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.
Answer 1
6. NOTIFICATION TO FDNY IS NOT REQUIRED,
PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN HOURS.
Answer 8
7. FOR UNPLANNED
REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMME- DIATELY
REPORT CONDITION TO THE AND THE FIRE DEPT.
Answer OWNER OF
THE BUILDING
8. I
F A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.
Answer 30
9. WHAT DOES "OOS" STAND FOR?
Answer OUT OF SERVICE
10. OOS
SYSTEMS SHALL BE IDENTIFIED BY PLACING AT FIRE
DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND
,CENTER
Answer TAGS
11. A SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES.
Answer MASTER FIRE SUPPRESSION PIPING CONTRACTOR
12. SHALL BE POSTED ON THE TAG INDICATING BOTH
STATIC AND FLOW PRESSURES BEFORE AND AFTER.
Answer DRAIN TEST RESULTS
13. GREEN TAGS INDICATE THAT .
Answer NO IMPAIRMENT WAS FOUND
14. GREEN TAGS WILL BE
PLACED ON THE .
Answer MAIN CONTROL VALVE
15. SY
STEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
TAG PLACED ON THE MAIN CONTROL VALVE.
Answer RED
16. A DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.
, Answer WHITE
17. A DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF
SERVICE.
Answer BLUE
18. THE
IMPAIRMENT COORDINATOR WILL NOTIFY THE
CARRIER, CENTRAL STATION AND OCCUPANTS.
Answer INSURANCE
19. PRIOR TO
RETURNING A SYS. TO SERVICE, THE SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
Answer IMPAIRMENT COORDI-
NATOR
20. GLYCERIN NOT GREATER THAN PERCENT OR
GLYCOL NOT GREATHER THAN PERCENT SHALL BE USED TO
PROTECT FROM FREEZ- ING.
Answer 50, 40
21. THE COF NUMBER AND SIGNATURE OF COF HOLDER
SHALL BE POSTED NEAR THE .