ICC 64 Property Maintenance and Housing Inspector
Exam||NEWEST EXAM!!! COMPLETE QUESTIONS
AND DETAILED SOLUTIONS LATEST UPDATE THIS
YEAR-JUST RELEASED.pdf||NEWEST EXAM!!!
A Feeder will be protected by fuses rated by 125 Amp.
What size AL EGC is required to be run in a raceway with
feeder supply conductors? - Answer-#4 AWG NEC
250.122
What load shall be provided for each20 Amp circuit
serving receptacles in a laundry area? - Answer-1500VA
NEC 220.51(A)
Given: Three appliances fastened in place are as follows:
Dishwasher rated at 1800VA, water heater at 6000 VA and
room C at 1600VA. what is the minimum-calculated
demand load for all appliances? - Answer-NEC 220.53 =
1.8kVA+6kVa+1.6kVa=9.4Kva X 100% =9400 VAD
What is the maximum percent of unbalance load to be
considered for a feeder neutral load regarding the
ungrounded feeder conductors in the supply electric
,2|Page
ranges, wall mounted ovens, counter top cooking units,
and electric dryer? - Answer-70% NEC 220.61(B)(1)
What is the maximum rating of any one cord and plug
connected utilization equipment when not fastened in
place and supplied by 15 amp branch circuit? - Answer-80
% NEC 210.23(A)(1)
Outlets installed for the purpose of charging EV shall be
supplied by _________branch circuit. - Answer-Individual
NEC 625.40
Ranges shall b supplied by a minimum branch circuit of
_________when the rating of ranges is 8.75kva or more. -
Answer-40AMP NEC 210.19(A)(3)
Penthouses constructed on buildings of other than Type I
Construction shall not exceed __ feet in height above the
roof deck. - Answer-18
(Section 1510.2.1 Height above roof deck)
In exterior walls and bearing partitions, any wood stud is
permitted to be cut or notched to a depth not exceeding __
percent of it's width. - Answer-25
, 3|Page
Section 2305.5.9
The ends of wood girders entering exterior masonry of
concrete walls shall be provided with a __ inch airspace
on top, side and end - Answer-1/2 inch
(Section 2304.12.2.1)
where an attic space is not provided with permeant stairs
or a ladder, protection for feeder cables running across the
face of the rafters in the attic shall only be required within
of the nearest edge of the attic entrance. - Answer-6 ft
NEC 334.23& 320.23 (A)
Termination provisions of equipment for circuits marked for
conductors ____________________shall be used for
conductors rated at a minimum of 75 degrees Celsius -
Answer-# 1 AWG NEC 110.14 (C)(1)(b)
what size EGC for 70 AMP circuit - Answer-# 8 AWG NEC
250.122
Footings for masonry fireplaces and their chimneys shall
be constructed of concrete or solid masonry at least __
inches thick. - Answer-12 inches