MOST RECENT EXAM 2026-2027 ACTUAL COMPLETE
REAL EXAM QUESTIONS AND CORRECT ANSWERS
(VERIFIED ANSWERS) ALREADY GRADED A+ |
GUARANTEED SUCCESS!! NEWEST EXAM | JUST
RELEASED!!
Testing a valve supervisory s/w, a signal shall indicate
movement from the
control valves normal position during either the first ____
revolutions or when
the stem has moved 1/5th of the distance from its normal
position - ANSWER -2
Control valve supervisory s/w shall be tested _____ - ANSWER -
Annually
Mechanical waterflow alarm devices shall be tested _____
- ANSWER -
Quarterly
System demand for class 2 standpipes shall be based on
_____ - ANSWER -
standards at the time of
installation
,A semi-auto dry standpipe without a backflow preventer shall
have a main drain
test _____ - ANSWER –
Annually
A small leak inside a stairwell during a hydrostatic test on a
manual standpipe is
a _____ - ANSWER -Non-Critical
deficiency
Air pressure supervision at a constantly manned location,
gauges are inspected
_____ - ANSWER –
Quarterly
A 5% degradation in the water supply during a main drain test
on an automatic
wet standpipe, is considered a _____ - ANSWER -
Impairment
Automatic and Manual standpipes require a 5 year full flow
test. - ANSWER -
False
When performing a hydrostatic test and inspecting the
standpipe, there is a hose rack that only swings out 60 degrees.
This is a _____ - ANSWER -NonCritical deficiency
, When water damage is a concern, performing an air test at
_____ PSI is
recommended before putting water on the system -
ANSWER -25
A pressure loss of 5 PSI is acceptable during a 5 yr hydrostatic
test. - ANSWER
-
False
A class 2 standpipe shall meet at least _____ GPM during
flow testing -
ANSWER -
100
Hose valve on class II standpipes testing frequency. _____ yrs -
ANSWER -3
Dry standpipe shows a drastic increase in water delivery time
from one test to the next could be caused by _____ - ANSWER -
corrosion in the system piping
Visual inspections on standpipe and hose system
components - ANSWER -
Annually
Manual Standpipe - ANSWER -fire department to supplies
water through the
FDC