GUIDE 2026/2027 COMPLETE
QUESTIONS WITH VERIFIED CORRECT
ANSWERS || 100% GUARANTEED PASS
<NEWEST VERSION>
1. Other than a Deputy State Fire Marshal of the Division of State Fire
Marshal, who may be permitted to enter during reasonable business hours to
inspect your gas industry to assure the safety of the public? - ANSWER ✔ A
member of the LP Gas Board
2. South Carolina's laws regarding the retail sale of propane to the public
require that the seller have a license from the LP Gas Board and...? -
ANSWER ✔ An individual certified as competent by the Division of State
Fire Marshal
3. According to the National Fire Protection Association Pamphlet (NFPA)
#58, what is the limit on a temporary installation? - ANSWER ✔ Not to
exceed 6 months from the date of installation
4. The ratio of Ethyl Mercaptan per 10,000 gallons of LP Gas by test shall be
how many lbs. per gallon? - ANSWER ✔ 1.0 lbs. per 10,000 gallons of LP-
Gas
,5. DOT containers shall be designed, fabricated, tested, and marked (or
stamped) in accordance with which organization? - ANSWER ✔ U.S.
Department of Transportation
6. Containers for general use shall not have individual water capacities greater
than how many gallons? - ANSWER ✔ 120,000 water gallons
7. Service station containers shall not have individual capacities greater than
how many gallons? - ANSWER ✔ 30,000 water gallons
8. In buildings under construction or repair, the total water capacity of
containers manifold together and serving any one heater shall not be greater
than what capacity? - ANSWER ✔ 735 pounds
9. In buildings undergoing minor renovations and visited by the public during
normal work hours, what is the maximum capacity of LP Gas that can be
present in this building? - ANSWER ✔ A 20 lb. container per worker
assigned to use LP Gas
10.The use of LP Gas in buildings for demonstration and/or training is limited
to a maximum water capacity of 5 pounds. If more than one such container
is used in classrooms, how much distance shall you have between
containers? - ANSWER ✔ 20 feet
11.The maximum LP Gas water capacity container that can be connected to any
one manifold at a single permanent installation located on a roof and using
portable containers is what? - ANSWER ✔ 400 lbs.
,12.All installations of LP Gas on roofs of buildings must be reported to what
agency? - ANSWER ✔ Local Fire Department
13.The maximum water capacity of a fuel container of LP Gas on an individual
forklift shall not exceed how many lbs? - ANSWER ✔ 105 lbs.
14.To store or service a vehicle powered by LP Gas inside a building, what
must be accomplished? - ANSWER ✔ The fuel system must be leak free
15.Smoking, open flames, metal cutting or welding, portable electrical tools and
extension lights capable of igniting LP Gas shall not be permitted within
what distance from an ASME container? - ANSWER ✔ 15 feet from point
of transfer
16.Indoor gas hose connector requirements - ANSWER ✔ Indoor gas hose
connectors shall be used only to connect laboratory, shop, and ironing
appliances requiring mobility during operation.
17.Outdoor gas hose connector requirements - ANSWER ✔ Where outdoor gas
hose connectors are used to connect portable outdoor appliances, the
connector shall be listed in accordance with ANSI Z21.54.
18.Flexible connection requirements - ANSWER ✔ Where flexible connections
are used, they shall be of the minimum practical length and shall not extend
from one room to another.
, 19.Manual shutoff valve requirement - ANSWER ✔ Each appliance connected
to a piping system shall have an accessible, approved manual shutoff valve
with a non-displaceable valve member.
20.Location of shutoff valve - ANSWER ✔ The shutoff valve shall be located
within 6 feet of the appliance it serves.
21.Gas convenience outlet requirements - ANSWER ✔ Gas convenience outlets
shall be listed in accordance with ANSI Z21.90/CSA 6.24 and installed in
accordance with the manufacturer's installation instructions.
22.Sediment trap installation - ANSWER ✔ Where a sediment trap is not
incorporated as a part of the appliance, a sediment trap shall be installed as
close to the inlet of the appliance as practicable.
23.Central heating furnace installation in bedrooms - ANSWER ✔ Central
heating furnaces and low-pressure boilers shall be installed in a closet
equipped with a weather-stripped door with no openings.
24.Central heating furnace installation requirements - ANSWER ✔ Shall
comply with specific conditions including installation in a closet with a
weather-stripped door and self-closing device.
25.Direct vent type boilers - ANSWER ✔ Central heating furnaces and low-
pressure boilers shall be of the direct vent type.