A 12 foot run of horizontal conduit between two enclosures ( one is dust- and ignition - proof
and the other is not) located in a class II, Division I location is required to have a minimum of
how many sealing fittings? - ✔✔✔-0
article 502.15
A 240 volt, twist - lock RECEPTACLE installed on a TEMPORARY power system of a construction
site would require which of the following?
A) GFCI protection
B) AFCI protection
C) LCDI protection
D) No protection or testing required - ✔✔✔-Gfci protection
(article 590.6 (B) (1) )
A device that requires a portable ladder for access, but does NOT require removal of the
structure, is defined as being?
A) Accessible
B) Unaccessible
C) Simi- accessible
D) Readily accessible - ✔✔✔-Accessible
(article 100)
A dry - type TRANSFORMER may be LOCATED in a suspended ceiling space where it is not ready
ACCESSIBLE if the voltage is 600 volts or less and has a maximum rating of ____________ kva
,Msater Electrician Test 211 Exam with Questions and Answers – 100% Solved
A) 10
B) 25
C) 50
D( 112 - ✔✔✔-50
(article 450.13 (B) )
A group of devices that serve to govern in some predetermined manner the electric power
delivered to the apparatus to which it is connected is a ?
A) Device
B) Controller
C) Disconnect
D) Circuit breaker - ✔✔✔-Controller
(article 100)
A listed assembly of two , three, or four insulated circuit conductors within a NONMETALLIC
jacket, an extruded thermoplastic covering, or a sealed nonmetallic covering that can be
mounted directly on the surface of walls and ceilings is the definition for:
A) Flat conductor cable
B) Flat cable assemblies
C) Nonmetallic sheath cable
D) Concealable nonmetallic extension - ✔✔✔-Concealable nonmetallic extension
, Msater Electrician Test 211 Exam with Questions and Answers – 100% Solved
(article 382.2)
A SERVICE head can be located no further away from the point of attachment than
____________ inches
A) 18
B) 24
C) 36
D) 48 - ✔✔✔-24"
(article 230.54) (C) (exceptions)
ACCEPTABLE METHODS of connecting GROUNDING and BONDING conductors include all the
following, EXCEPT:
A) Solder joints
B) Terminal bars
C) Exothermic weld
D) Listed pressure connectors - ✔✔✔-solder joints
(article 250.8 (A)
All 15 - and 20 - ampere, 125 - volt, general - purpose receptacles in a new dwelling are required
to be: - ✔✔✔-Grounding - type
article 406.4 (A)