QUESTIONS AND SOLUTIONS GRADED A+
●● Manual actuators shall not have a force more than.
Answer: 40lbs
●● Manual actuators shall not have a movement of more than.
Answer: 14 inches
●● Instructions with pictographs and lettering shall be atleast.
Answer: 1/4 inches
●● Pipe and fittings shall be made of.
Answer: Non combustible materials
●● galvanized pipe and fittings.
Answer: Shall not be used
●● During assembly examine pipe.
Answer: Internally to detect and remove contaminants
●● Readily acces means for manual actuators.
,Answer: Shall be located in a path of egress
●● Manual actuators shall be installed.
Answer: No more than 48in and no less than 42in
●● Fusible links shall be located.
Answer: At above each cooking appliance
●● Fusible links shall be.
Answer: 12 in in front of said item
●● A test shall be used on pipe using.
Answer: Nitrogen or dry air not exceeding normal operating pressure
●● Piping shall not.
Answer: Be hydrostatic tested
●● Owners inspection.
Answer: Monthly
●● Owners inspection records shall be retained.
Answer: Semi-annualy
, ●● Wet chemical fire extinguisher service at.
Answer: Every 6 months
●● Wet chemical fire extinguishing system service at.
Answer: 6 months
●● wet chemical fire extinguishing system with fire
damage,corrosion,welds etc.
Answer: Shall be hydrostatic tested
●● Maintenance reports shall be kept.
Answer: For a year
●● Fixed temperature sensing elements otger than fusible metal alloys
shall be replaced.
Answer: Every 12 months
●● Fixed temperature sensing elements of fusible metal alloys shall be
replaced.
Answer: Semi-annualy
●● Wet chemical extinguisher hydrostatic test.