ICC E2 Commercial Electrical Inspector Exam||Verified
Exam!!!|| Questions with Correct Answers and
explanations LATEST THIS YEAR -JUST
RELEASED.pdf||NEWEST EXAM!!!
Kitchen receptacles shall be supplied by not fewer than
how many small-appliance branch circuits? - Answer-2
(210.52(B)(3); 210.11(C)(1))
What minimum width of countertop requires a receptacle?
- Answer-12 in (210.52(C))
Countertop spacing: no point along the wall line shall be
more than what distance from a receptacle? - Answer-24
in (210.52(C)(1))
For an 80 in counter with a 24 in sink cutout, how many
receptacles are required? - Answer-2 (210.52(C)(1) &
Exceptions)
Countertop receptacles not counted if more than how far
above the countertop? - Answer-20 in (210.52(C)(3)(1))
,2|Page
Countertop receptacles not counted if more than how far
below the countertop? - Answer-12 in (210.52(C)(3)(3))
Countertop receptacles shall not be located where the
work surface overhangs more than what distance beyond
its support base? - Answer-6 in (210.52(C)(3)(3))
At least one bathroom receptacle shall be within what
distance of the outside edge of each basin? - Answer-36 in
(210.52(D))
Garages with electric power shall have at least how many
receptacles? - Answer-At least one receptacle outlet in
each car bay, not more than 5.5 ft above floor
(210.52(G)(1))
Each accessory building with electric power shall have at
least? - Answer-One receptacle outlet (210.52(G)(2))
In any dwelling unit, hallways 10 ft or more in length shall
have at least? - Answer-One receptacle outlet (210.52(H))
, 3|Page
No point measured horizontally along the floor line of any
wall space shall be more than how far from a receptacle? -
Answer-6 ft (210.52(A)(1))
Wall space (for required receptacles) includes any wall
with what minimum width? - Answer-2 ft (210.52(A)(2)(1))
Floor receptacles count toward required receptacles only if
within how far of the wall? - Answer-18 in (210.52(A)(3))
What minimum branch-circuit size is permitted for a
kitchen refrigerator? - Answer-15 A (210.52(B) Ex 2)
A 125 V, 15- or 20-A service receptacle shall be installed
within how far of HVAC equipment to be serviced? -
Answer-25 ft (210.63)
For indoor locations, the required service receptacle shall
be located where? - Answer-In the same room as the
equipment (210.63(B)(1))