1. When emergency power is provided to a Group I-2
occupancy, what is the MINIMUM amount of time that the
emergency power shall be available? - Answer-*1104.5.1
Emergency power duration and installation.* "... In Group
I-2, the emergency power system shall provide power for
not less than *90 minutes* and consist of storage
batteries...
2. In a building that is sprinklered and used for
combustible material storage, what MINIMUM distance
below the sprinkler head deflectors shall the materials be
maintained? - Answer-*315.3.1 Ceiling clearance.* "... a
minimum of *18 inches* below sprinkler head deflectors in
sprinklered areas of buildings."
3. What is the MINIMUM separation between an above
ground 60,000 gallon LP-Gas storage container and
buildings, public ways, or lot lines of adjoining property
that could have a building constructed upon it? - Answer-
*Table 6104.3. 75'*
,2|Page
4. In a non-sprinklered building that has high-piled
storage, what is the MINIMUM width of the aisles? -
Answer-*3206.9.1.2 Nonsprinklered buildings* "Aisles in
nonsprinklered buildings shall be a minimum of *96 inches
wide.*
5. What is the MINIMUM distance that a recreational fire
can be conducted from a structure? - Answer-*307.4.2
Recreational fires.* "Recreational fires shall not be
conducted within *25 feet* of a structure or combustible
material..."
6. What is the MAXIMUM size air supported temporary
membrane structure that can be erected without a permit?
- Answer-*105.7.16 Temporary membrane structures and
tents.* "A construction permit is required to erect an air-
supported temporary membrane structure or a tent having
an area in excess of *400 square feet.*
7. Fire sprinkler heads installed in an area where
flammable vapor residue can accumulate on heads shall
be protected by means of a protective bag made of any of
the following materials: - Answer-*2404.5.2 Protection of
,3|Page
sprinklers.* "...Bags used as a protective covering shall be
0.003-inch-thick *polyethylene or cellophane or shall be
thin paper*..."
8. Cryogenic piping shall be tested to be free of leaks with
a pneumatic test. The piping shall be tested at - Answer-
*5505.1.2.6 Testing.* "...*110 percent* when testing is
conducted *pneumatically.*
9. When a mechanical ventilation alternative is used for
smoke proofing a vestibule, what is the MINIMUM fire
protection rated allowed for the doors? - Answer-*IBC
909.20.4.1. 120 minute* rating
10. In the area where hot work is being done, what
MAXIMUM distance from the work shall a fire extinguisher
be located? - Answer-*3504.2.6 Fire extinguisher.* "A
minimum of one portable fire extinguisher complying with
Section 906 and with a minimum 2-Al20-B:C rating shall
be readily accessible with *30 feet* of the location where
hot work is performed.
11. What is the MAXIMUM size cold deck used for a log
storage area? - Answer-*2806.2 Cold decks.* Cold decks
, 4|Page
shall not exceed *500 feet in length, 300 feet in width and
20 feet in height.* Cold decks shall be separated from
adjacent cold decks or other exposures by a minimum of
100 feet.
12. What is the MAXIMUM size of a tire warehouse before
an automatic sprinkler system throughout the building is
required? - Answer-*IBC 903.3.9.2.* 20,000 cubic feet.
13. Which of the following occupancies does not allow for
the storage or use of Class liquid and solid oxidizers? -
Answer-*6303.1.1.1.2 Group R occupancies.* Class 4
liquid and solid oxidizers shall not be stored or used within
*Group R occupancies.*
14. How long after hot work has been completed on a job
site can the FCO requires to view the permit? - Answer-
*3503.3 Hot work program permit.* Hot work permits,
issued by an approved responsible person under a hot
work program, shall be available for review by the FCO at
the time the work is conducted and for *48 hours after
work is complete.*