NICET 1 EXAM QUESTIONS AND ANSWERS
GRADED A+!!
A hard hat is required on a job site when _____?
OSHA answer >>> There is a danger from falling objects
Any condition occurring in a communications or transmission channel that
interferes with the proper transmission or interpretation or both of status change
signals at the supervising station is known as _____? a
NFPA 72-3.3.9 answer >>> Adverse condition
A 4"x 4" box has multiple FPL cables pulled through it. A minimum of _____ inches
of cable should be available for splicing?
NFPA 70-300.14 answer >>> 6
Wiring installed underneath a corrugated metal roof shall maintain a minimum
separation of _____ inches?
NFPA 70-300.4(E) answer >>> 1.5
According to NFPA 72, the system account number is located in section _____ of
the record of completion?
, NICET 1
NFPA 72-Figure 7.8.2(a) answer >>> 2
Consider a circuit with a resistance of 6 ohms and a current of 2 amperes. What is
the voltage? answer >>> 12 volts
All means of interconnecting equipment, devices, and appliances, and wiring
connections shall be monitored for the integrity of the interconnecting
conductors or equivalent so that the occurrence of a single open or a single
ground fault condition in the installation conductors or other signaling channels is
automatically indicated within _____ seconds?
NFPA 72-12.6.1 answer >>> 200
Pathway survivability level _____ shall consist of pathways and buildings that are
fully protected by an automatic sprinkler system with 2-hour fire rated circuit
integrity cable?
NFPA 72-12.4.4 answer >>> 3
What is the minimum conductor size for Power Limited Fire Alarm cable which is
single conductor?
NFPA 70-760.179(B) answer >>> 18 AWG
According to NFPA 72, the maximum flash rate for a visible notification appliance
shall not exceed _____ flashes per second?
NFPA 72-18.5.3.1 answer >>> 2
Consider the installation of rigid metal conduit. Where conduit is threaded in the
field, a standard cutting die with a 1 in _____ taper shall be used?