What size dual element (time delay) fuse is need for a 40 Horsepower, 480 volt, 3-
phase wound rotor motor? -ANSWERS-80amps 430.52.C exc 1 - round up
What size THWN copper conductors are nedded for a 40 Horsepower, 480 volt, 3-
phase wound rotor motor? -ANSWERS-6awg using 75
What is the maximum size inverse time circuit breaker needed for a 25 horsepower, 480
volt, 3 phase, squirrel cage, code letter D motor -ANSWERS-90a round up for standard
size
What is the maximum size nontime delay fuse needed for a 25 horsepower, 480 volt, 3
phase, squirrel cage, code letter E motor -ANSWERS-110amps standard fuse size
In addition to the number of branch circuits required, in dwelling units,___ or more
small-appliance branch circuits shall be provided. -ANSWERS-2 210.11.C1
In addition to the number of branch circuits required, in dwelling units, at least___ 120
volt, 20 ampere branch circuit shall be installed to supply receptacle outlets in attached
garages and detached garages with electrical power. -ANSWERS-1 210.C4
Electrical equipment shall be installed -ANSWERS-neat and workmanlike manner
110.12
, A Delta High-Leg shall be durably and permanently marked by an outer finish that is___
in color or by other effective means. -ANSWERS-orange 110.15
Isolated ground receptacles shall be identified by a___ located on the face of the
receptacle -ANSWERS-orange triangle 406.3.D
Receptacles that are controlled for by an automatic control device for the purpose of
energy management shall be marked with the word(s)___? -ANSWERS-controlled
406.3.E
What is the box fill requirement for a box that has three 12-3 w/G, NM cable, with one
device, two Romex connectors and three clamps? -ANSWERS-29.25" t314.16.B
A 200 amp residential service uses 2/0 AWG copper service entrance conductors, the
minimum size grounding electrode conductor is___ AWG copper -ANSWERS-4awg
t250.66
Two conduits installed in parallel contain 4 - 500KCMIL THN copper conductors, the
neutral conductor carries only the unbalanced current from other conductors of the
same circuit, what size overcurrent protection with 75°C terminals is needed? -
ANSWERS-800 amp rule
Four conduits installed in parallel contain 4 - 500KCMIL THHN copper conductors, the
neutral conductor carries only the unbalanced current from other conductors of the
same circuit, what size overcurrent protection with 75°C terminals is needed? -
ANSWERS-1200a t240.6.A 240.4.C
The cross-sectional area of the conductors permitted in a seal shall not exceed___
percent of the cross-sectional area of the rigid metal conduit, unless the seal is specially
listed for a higher % of conductor fill. -ANSWERS-25% 501.15.C6
The minimum size service entrance conductor for a 100-amp mobile home service
is___awg copper. -ANSWERS-4awg p.800 Annex D