1. Unlawful to be installed - ANSWER ✔ Devices that give the physical
appearance of fire protection equipment (ex. CCTV sprinkler head)
2. Minimum amount of time records must be kept - ANSWER ✔ 3 years
3. Hydro static test must be performed - ANSWER ✔ Every 5 years
4. System fully out of service - ANSWER ✔ Tag/red Disc/White
5. System partially out of service - ANSWER ✔ Tag/Red. Disc/Blue
6. System free from defects - ANSWER ✔ Tag/Green. Disc/N/A
7. S12/S15 holder may perform - ANSWER ✔ Visual inspections, proper
notifications and record inspection results
8. S12/S15 with Q99/01 May perform - ANSWER ✔ Visual inspections, test
notification appliances, perform daily and weekly routine maintenance and
record inspection results
9. MFSPC - ANSWER ✔ Master fire suppression piping contractor
10.MP - ANSWER ✔ Master plumber
11.MFSPC w/s12/15 can - ANSWER ✔ Inspect, test, maintain and
repair/replace system components
,12.MP with S12/15 can only work on - ANSWER ✔ Residential with 30
sprinkler heads or less and no booster pump
13.Deluge system - ANSWER ✔ All sprinkler heads are open, pipes dry
14.ELO extra large orifice sprinkler - ANSWER ✔ Orifice size greater than 1"
15.Extended coverage sprinklers head - ANSWER ✔ Covers max 400sqft in
light hazard and 144sqft for high hazard areas
16.RTI of a standard sprinkler - ANSWER ✔ 80
17.Sprinkler system with open heads - ANSWER ✔ Deluge system
18.Freezing point of antifreeze solutions - ANSWER ✔ Hydrometer or
refractometer
19.Color required for sprinkler and standpipe risers per local law 58/2009 -
ANSWER ✔ Yellow
20.Distance for hanger assembly to center line of an upright sprinkler head -
ANSWER ✔ 3 inches
21.Location of the automatic ball drip - ANSWER ✔ Between lower check
valve and fire department connection
22.Purpose of a ball drip - ANSWER ✔ To prevent freezing in the line
23.Build up of foreign matter on a sprinkler head - ANSWER ✔ Loading
24.When a sprinkler head opens - ANSWER ✔ It is said to be fused
25.Minimum air pressure inside a pressure tank - ANSWER ✔ 75 psi
26.Height a gravity tank should be above highest sprinkler heads it supplies -
ANSWER ✔ 25 feet
,27.Frequency for replacing gauges - ANSWER ✔ Every 5 years
28.Number of spare sprinkler heads required when under 300 sprinklers -
ANSWER ✔ 6
29.Number of spare sprinkler heads required when there are 300 to 1000
sprinklers - ANSWER ✔ 12
30.Number of spare sprinkler heads required when there are over 1000
sprinklers - ANSWER ✔ 24
31.Year all sprinklers prior to which shall be replaced - ANSWER ✔ 1920
32.GPM at which house pumps fill the gravity tank - ANSWER ✔ 65 gpm
33.Spray pattern of a sprinkler 3 feet below the sprinkler head deflector -
ANSWER ✔ 16 feet at 15 gpm
34.Notification time to FDNY for an out of service condition - ANSWER ✔ 8
hours
35.Who must draw a hand drawn sketch of the compactor system - ANSWER
✔ Certificate of fitness holder
36.Upright Sprinkler - ANSWER ✔ A sprinkler designed to be installed in
such a way that the water spray is directed upwards against the deflector.
37.Water Spray Fixed System - ANSWER ✔ A special fixed pipe system
connected to a reliable fire protection water supply and equipped with water
spray nozzles for specific water discharge and distribution over the surface
or area to be protected. The piping system is connected to the water supply
through an automatically or manually actuated valve that initiates the flow of
water. An automatic valve is actuated by operation of automatic detection or
manual release equipment installed in the same areas as the water spray
nozzles. (In special cases, the automatic detection system may also be
located in another area.)
, 38.PREACTION SPRINKLER SYSTEMS - ANSWER ✔ designed for
situations where there is danger of serious water damage. Water damage is
usually caused by damaged sprinklers or broken piping. Under normal
conditions there is no water in the piping. The air in the piping may or may
not be is under pressure. A preaction valve prevents the water from entering
the system. The valve is automatically opened when a fire detection system
discovers that there is a fire or smoke condition. The preaction valve is
tripped by the fire detection system before any of the sprinkler heads open.
A supervisory device signals when the valve is opened. The preaction valve
can also be operated manually.
39.DELUGE SPRINKLER SYSTEMS - ANSWER ✔ equipped with open
sprinkler heads designed to wet down an entire area involved in a fire. This
system is needed when there is danger of a fire rapidly spreading throughout
the building. The deluge system will slow down the spread of the fire.
Deluge systems are suitable for hazardous occupancies. This includes
buildings in which flammable liquids or other hazardous materials are
handled or stored.
The sprinkler heads in the deluge system are open at all times. Under normal
conditions there is no water in the piping. The air in the piping is not under
pressure. A closed control valve prevents water from flowing into the
system. A fire detection device automatically opens the control valve when a
fire is identified. A supervisory device signals when the valve is opened.
When the valve is opened water flows into the system. The water is then
discharged out all of the sprinkler heads. The water control valve may also
be opened manually.
40.NON-AUTOMATIC DRY SPRINKLER SYSTEMS - ANSWER ✔ ll
pipes are normally dry. Water is supplied when needed by pumping water
into the system through the Fire Department connection. Some of these
systems are supplied by manual operation of a water control valve and may
be equipped with sprinklers with or without fusible links.
There are several non-automatic systems: 1) Perforated pipe systems - a
single line of piping drilled at intervals for water discharge. These systems
are usually found in basements or other areas difficult to reach in fire
fighting operations. 2) Open fixed spray nozzles for transformer vaults or
other hazardous areas; 3) exterior exposure sprinklers (or window sprinklers)
use open sprinkler heads to form an external water curtain on the walls of a