TFM03 TEST EXAM QUESTIONS AND
ANSWERS 2026 VERIFIED.
Operating devices shall operate at - ANS 32F to 120F
Manual actuators shall not have a force more than - ANS 40lbs
Manual actuators shall not have a movement of more than - ANS 14 inches
Instructions with pictographs and lettering shall be atleast - ANS 1/4 inches
Pipe and fittings shall be made of - ANS Non combustible materials
galvanized pipe and fittings - ANS Shall not be used
During assembly examine pipe - ANS Internally to detect and remove contaminants
Readily acces means for manual actuators - ANS Shall be located in a path of egress
Manual actuators shall be installed - ANS No more than 48in and no less than 42in
Fusible links shall be located - ANS At above each cooking appliance
@COPYRIGHT ALL RIGHTS RESERVED PAGE 1 OF 9
, Fusible links shall be - ANS 12 in in front of said item
A test shall be used on pipe using - ANS Nitrogen or dry air not exceeding normal operating
pressure
Piping shall not - ANS Be hydrostatic tested
Owners inspection - ANS Monthly
Owners inspection records shall be retained - ANS Semi-annualy
Wet chemical fire extinguisher service at - ANS Every 6 months
Wet chemical fire extinguishing system service at - ANS 6 months
wet chemical fire extinguishing system with fire damage,corrosion,welds etc - ANS Shall be
hydrostatic tested
Maintenance reports shall be kept - ANS For a year
Fixed temperature sensing elements otger than fusible metal alloys shall be replaced -
ANS Every 12 months
Fixed temperature sensing elements of fusible metal alloys shall be replaced - ANS Semi-
annualy
Wet chemical extinguisher hydrostatic test - ANS In 12 years
@COPYRIGHT ALL RIGHTS RESERVED PAGE 2 OF 9
ANSWERS 2026 VERIFIED.
Operating devices shall operate at - ANS 32F to 120F
Manual actuators shall not have a force more than - ANS 40lbs
Manual actuators shall not have a movement of more than - ANS 14 inches
Instructions with pictographs and lettering shall be atleast - ANS 1/4 inches
Pipe and fittings shall be made of - ANS Non combustible materials
galvanized pipe and fittings - ANS Shall not be used
During assembly examine pipe - ANS Internally to detect and remove contaminants
Readily acces means for manual actuators - ANS Shall be located in a path of egress
Manual actuators shall be installed - ANS No more than 48in and no less than 42in
Fusible links shall be located - ANS At above each cooking appliance
@COPYRIGHT ALL RIGHTS RESERVED PAGE 1 OF 9
, Fusible links shall be - ANS 12 in in front of said item
A test shall be used on pipe using - ANS Nitrogen or dry air not exceeding normal operating
pressure
Piping shall not - ANS Be hydrostatic tested
Owners inspection - ANS Monthly
Owners inspection records shall be retained - ANS Semi-annualy
Wet chemical fire extinguisher service at - ANS Every 6 months
Wet chemical fire extinguishing system service at - ANS 6 months
wet chemical fire extinguishing system with fire damage,corrosion,welds etc - ANS Shall be
hydrostatic tested
Maintenance reports shall be kept - ANS For a year
Fixed temperature sensing elements otger than fusible metal alloys shall be replaced -
ANS Every 12 months
Fixed temperature sensing elements of fusible metal alloys shall be replaced - ANS Semi-
annualy
Wet chemical extinguisher hydrostatic test - ANS In 12 years