TEST QUESTIONS AND CORRECT ANSWERS
COMPLETE SOLUTION VERIFIED PASS
●● By definition an "underground storage tank system" includes
a.) The tank, all connected piping and dispensers
b.) The tank, all connected piping, ancillary equipment and containment
system
c.) Only the tank
d.) Only tanks totally beneath the surface of the ground
Answer: b.) The tank, all connected piping, ancillary equipment and
containment system
(H&SC, Sec 25281(z))
●● Under-dispenser containment was required for all UST systems by
___________.
a.) December 31, 2003
b.) July 1, 1987
c.) January 1, 1984
,d.) January 1, 2000
Answer: a.) December 31, 2003
CCR Title 23, Sec 2636(g)(C)
●● According to California Law, UST systems installed after July 1,
2003, require a one-time ELD test to ensure that the tank is product
tight...
a.) If the tank is located within one (1) mile of a public drinking water
well
b.) If the tank is located within 1000 feet of a public drinking water well
c.) Unless the tank is equipped with secondary containment
d.) In all cases
Answer: For ALL tanks before use (H&SC 25290.2 (I))
d.) In all cases
H&SC, Sec 25290.2(i)
●● The written report submitted to the local agency after an
unauthorized release is required to include the following except:
a.) Description of actions taken to stop the release
,b.) Cause of the release
c.) Method of disposal of released product
d.) Date on which the release was discovered
Answer: b.) Cause of the release
CCR Title 23, Sec 2652(c)
●● An unauthorized release which does not escape from secondary
containment only requires a record on the operator's monitoring reports
provided:
A. It did not increase the hazard of fire
B. It did not cause any deterioration of the secondary containment
C. It was cleaned up within 8 hours of detection
D. All of the above
Answer: D. All of the above
H&SC, Sec 25294
●● The annual monitoring certification may be performed by:
A. A person possessing the appropriate contractors licenses
, B. An individual trained and certified by the manufacturer of the
monitoring equipment
C. A designated UST operator
D. A person who meets the requirements of both a and b
Answer: D. A person who meets the requirements of both a and b
CCR Title 23, Sec 2715(i)
●● The following is true of secondary containment testing, EXCEPT:
a.) Must be tested every 24 months
b.) Must be tested every 36 months
c.) Results must be submitted to the local agency within 30 days of
testing
d.) Local agency must be notified 48 hours prior to testing
Answer: a.) Must be tested every 24 months
CCR Title 23, Sec 2637(a)
●● Records of cathodic protection system maintenance must be kept on
file for ______________.
a.) 10 years