Part 1: Next-Generation Refrigerants, Regulations & Safety (15 Questions)
1. A technician is retrofitting a commercial DX system originally designed for
R-22. Which refrigerant is classified as an A1 (lower toxicity, no flame
propagation) "non-ozone depleting" substitute with a GWP of approximately
675?
A. R-410A
B. R-32
C. R-454B [Correct Answer]
D. R-744
Rationale: R-454B is an HFO blend with an A2L (mildly flammable)
classification, but it is the direct R-22 substitute with a GWP of 466-675. R-410A
has a GWP of 2088. R-32 is A2L (not A1). R-744 is CO2 (high pressure, A1).
2. According to EPA Section 608 regulations updated for 2026, what is the
mandatory maximum allowable leak rate for industrial process refrigeration
,(IPR) systems containing 50+ lbs of high-GWP refrigerant?
A. 15%
B. 30% [Correct Answer]
C. 45%
D. 75%
Rationale: The EPA updated leak repair requirements under the American
Innovation and Manufacturing (AIM) Act. As of 2026, IPR systems have a 30%
threshold, while commercial comfort cooling remains at 20% .
3. When using R-32 (A2L) in a split system, what specific safety requirement
must the indoor unit satisfy to comply with UL 60335-2-40?
A. The indoor unit must have a metal fan blade.
B. The indoor unit must include a refrigerant detection system (RDS) with
mitigation. [Correct Answer]
C. The unit must be painted red to indicate flammability.
D. The suction line must be insulated with neoprene only.
Rationale: UL 60335-2-40 now requires that for indoor units using A2L
refrigerants, a Refrigerant Detection System (RDS) must shut down the unit and
activate airflow if a leak is detected to prevent combustion.
4. What is the primary environmental driver for the shift from R-410A to R-
32 and R-454B in 2025-2026?
A. Ozone Depletion Potential (ODP)
B. Global Warming Potential (GWP) [Correct Answer]
C. Flammability index
D. Oil miscibility
Rationale: R-410A has a GWP of 2088. International regulations (Kigali
Amendment) mandate phasedowns of high-GWP HFCs, pushing the industry
toward lower-GWP alternatives like R-32 (GWP 675).
5. During a recovery process on a system with an unknown refrigerant, the
gauge pressure rises rapidly after the recovery machine stops. What is the
most likely cause?
A. The vacuum pump is losing oil.
B. Non-condensables (air) are present in the system. [Correct Answer]
C. The compressor is short-cycled.
D. The filter drier is restricted.
Rationale: Non-condensables (air) do not condense under ambient temperatures.
, As the system pressure equalizes, the "vapor pressure" of the trapped air causes the
standing pressure to spike rapidly.
6. Which of the following refrigerants is classified as "natural" and requires
high-side pressures typically exceeding 1,200 psi in warm climates?
A. R-134a
B. R-744 (Carbon Dioxide) [Correct Answer]
C. R-1234yf
D. R-290
Rationale: R-744 operates transcritically. Triple-point pressures are extremely
high, often exceeding 1,800 psi, requiring specialized high-pressure fittings and
sensors.
7. A technician using a recovery cylinder must never exceed what percentage
of the cylinder's "water capacity" (WC) rating to avoid hydraulic rupture?
A. 50%
B. 80% [Correct Answer]
C. 90%
D. 95%
Rationale: The Department of Transportation (DOT) mandates that refrigerant
cylinders must not exceed 80% liquid fill to allow for thermal expansion.
8. In the context of HVAC safety, what does the "L" in "A2L" signify?
A. Low pressure
B. Low flammability [Correct Answer]
C. Lubricated refrigerant
D. Life safety
Rationale: ASHRAE Standard 34 classifies refrigerants by Toxicity (A/B) and
Flammability (1, 2L, 2, 3). "2L" signifies a lower flammability than class 2, with a
burning velocity of < 10 cm/s.
9. What tool is required by law to be used before opening a sealed
refrigeration circuit to prevent emissions?
A. Nitrogen regulator
B. Recovery machine & certified recovery cylinder [Correct Answer]
C. Micron gauge
D. Leak detector
Rationale: It is illegal to vent refrigerants (with few de minimis exceptions). EPA