revision
Which set of documentation is required to be maintained and retained for the life of the system?
as built drawings, hydraulic calculations, original acceptance test records, and device manufacturer's
data sheets
as built drawings, hydraulic data plate, and annual maintenance and test records
inspection reports, test records, and maintenance as required by the standard
installation drawings, permit applications, and submittals signed by the Authority Having Jurisdiction
(AHJ) - CORRECT ANSWERS-a
What provisions must be made for a main drain test?
shut down fire pump
shut down jockey pump
shut down main control valve
verify adequate drainage - CORRECT ANSWERS-c
Which set of steps are taken when an inspector notices that the air gauge on a freezer is lower than the
air gauge on a supply/air compressor?
The air line in service is shut down and the ice block is removed. If the ice block cannot be totally
removed then the alternate air line is opened and used.
The dry valve or pre-action system is shut down and the air lines are dismantled to remove the ice block.
The gauges are replaced with new gauges. If the gauges still do not match pressure, the alternate air line
is opened to increase pressure.
The inspector takes the in-service air line out of service and the alternate air line is opened to equalize
the pressure on the system. The out-of-service air line is taken apart and the ice block is removed and
used as future alternate air line. - CORRECT ANSWERS-d?
In a building with multiple wet pipe systems, for how many systems and at what frequency are internal
inspections of piping required?
, every other system every 2 years
every other system every 5 years
every system every 2 years
every system every 5 years - CORRECT ANSWERS-b
After an impariment has been restored, who shall verify that all conditions have been addressed in
order to remove an impairment tag?
alarm company representative
Authority Having Jurisdiction (AHJ)
fire department official
impairment coordinator - CORRECT ANSWERS-d
An inspection company is performing its first inspection of an existing warehouse owned by a new
client. The warehouse has rack storage with large sprinklers near the roof. The spare sprinkler cabinet is
empty. The sprinklers near the roof are within 20 to 28 inches from the top of the storage.After noting
that the sprinkler cabinet needs to be replenished, what should be recommended?
call for an engineering evaluation
have the storage moved down to a 36-inch clearance
have the storage moved down to a 48-inch clearance
no further action is needed; the head clearance is correct - CORRECT ANSWERS-a?
During a 5-year internal inspection on an alarm valve, what areas or devices will the inspector inspect?
airline strainer and air compressor drip legs
clapper, trim ports, and water motor gong assembly
FDC caps, swivels, and piping and check valves
strainers, filters, and restriction orifices - CORRECT ANSWERS-d