Where located above floor (within 2.1m or 7ft.) cables
shall be securely fastened at intervals of? - Answer-not
more than 18 inches
Which cable types can be installed in fireproof riser
shafts? - Answer-FPLP, FPLR, and FPL
For systems employing relocation or partial evacuation, a
_______ or _______ pathway survivability shall be
required for in-building pathway survivability - Answer-
Level 2
Level 3
Central station service, which consists of the following
elements: - Answer-Runner service
The central station service elements shall be provided
under contract to a subscriber by a ________ that has a
,2|Page
listing for central station fire alarm services - Answer-prime
contractor
The central station shall have not less than ______
qualified operators on duty at the central station at all
times to ensure disposition of signals in accordance with
the requirements of 26.3.8 - Answer-two
Complete records of all signals received shall be retained
for at least ________. - Answer-1 year
The protected property shall be either a contiguous
property or noncontiguous properties under one
ownership. - Answer-Proprietary Supervising stations
Drawings which have been approved by the AHJ for a fire
alarm project are commonly referred to as _____
drawings? - Answer-Shop
A project requires photoelectric spot type smoke detectors.
Which of the following environmental conditions typically
will affect photoelectric smoke detector response? -
Answer-Humidity greater than 93%
, 3|Page
Consider a Group M where the entire building is one-story
at the level of exit discharge. A fire alarm system is
required when the occupant load is _____ or greater? -
Answer-500
Consider the use of smoke detectors on a level ceiling
with beams where the ceiling height is 10 feet AFF. For a
beam depth of less than _____ inches smooth ceiling
spacing shall be permitted? - Answer-12
An acceptable substitute for FPLP is _____? - Answer-
CMP
Consider NPLFA cable. The minimum conductor size is
_____ AWG? - Answer-18 solid or stranded
Consider the installation of a visible notification appliance
in a corridor which is 15 feet wide. Visible notification
appliances shall be located not more than _____ feet from
each end of the corridor? - Answer-15