According to NFPA 72 how many spot type heat detectors
are required for a space that is 80' long and 55 floor wide
with a smooth 10' ceiling? the detector is listed for a
maximum space between detectors of 30' - Answer-6
What color code requirement for a spot type heat detector
rated at 200゚F - Answer-White (NFPA 72, Table 17.6.2.1)
Unless otherwise recommended by the manufacturers
published instructions single and multiple stations smoke
alarms installed in one and 2 family dwellings shall be
replaced every - Answer-10 years from the day-of
manufacture. (NFPA 72, 14.4.7.1)
Fire alarm cables are permitted to be strapped to conduit
to support the cable - Answer-False (NEC 760.143)
,2|Page
Where non power limited wiring is installed exposed it
must be mechanically protected within_____of the finished
floor - Answer-7' ft
Fire-Warning equipment to be installed in residential
occupancies shall produce the audible emergency
evacuation signal described in - Answer-ANSI S3.41
According to NFPA 72, visible notification appliance for
non-sleeping areas must be mounted between ___ and
___ inches above the finished floor - Answer-80 & 96
If system impairment occurs, the owner must be notified
___ within ___ - Answer-in writing & within 24 hours
A 20 X 20' ft room with a 20'ft high ceiling requires at a
minimum a ___ ceiling mounted strobe - Answer-30
candela
According to NFPA 72, a 40 x 40'ft room or area with a
10'ft ceiling is best covered by a ___ cd visible notification
appliance, centered on one wall. - Answer-60
,3|Page
Conductors returning to the fire alarm control panel
(FACP) from the last field device on the circuit might
indicate a _____ circuit - Answer-Class A
Secondary power supplies for an emergency voice/alarm
communication fire alarm system shall be capable of
operating for minimum of ___ of standby followed by ___
of alarm. - Answer-24 hrs & 15 mins
The fire alarm system primary power branch circuit
disconnecting means must be ___ in color. - Answer-Red
The secondary power supply for protected premises shall
automatically provide power within ___ seconds when
primary power fails. - Answer-10 seconds
Under which of the following conditions shall spot-type
smoke detectors NOT be installed? - Answer-When the
temperature is over 100*F
Who is responsible for maintaining Personal Protective
Equipment? - Answer-YOU, the employee
, 4|Page
What does GFCI stand for? - Answer-Ground Fault Circuit
Interrupter
A fixed-temperature, non-restorable spot type heat
detector shall be tested ____ from initial installation. -
Answer-15 years after
Heat detectors should be selected to operate at least ___
degrees Farenheit above the maximum expected ambient
temperature at the ceiling of the protected space. -
Answer-20*F
According to the NFPA 72, testing records of the fire alarm
system shall be kept until the next test and ____ year
thereafter. - Answer-1
Who is responsible for storing and maintaining testing
records of the fire alarm system? - Answer-The Owner of
the system
Household fire alarm system smoke detectors shall be
tested by a technician _______. - Answer-Annually