Conductors that supply a RESISTANCE WELDER shall be protected
by an overcurrent device rated or set at a maximum of _____________
percent of the conductor rating. - CORRECT ANSWER=300
article 630.32 (B)
Given: In a mobile - home park, the computed load for each mobile
home is 15,000 VA and the park will have 25 mobile homes. the service
will be a single main, 120/240 - volt service.
The electrical service required for this mobile - home park shall be at
least __________ amps. - CORRECT ANSWER=1600
The metal frame of a CIRCULATING POOL PUMP that is
,2 | Page
PERMANENTLY wired and located outside is required to : -
CORRECT ANSWER=Have GFCI protection
article 680.22 (A) (2)
Bare, green insulation or green with yellow stripes insulation is
generally used for which type of conductors? - CORRECT
ANSWER=Equipment grounding conductor
article 250.119
The maximum total rating of FASTENED IN PLACE utilization
equipment permitted on a 20 - ampere branch circuit that also serves
lighting is ___________ amps. - CORRECT ANSWER=20
article 210.23 (A) (2)
On a 20 - ampere small - appliance circuit with three outlets, what rating
of receptacles is permitted? - CORRECT ANSWER=20 amperes only
table 210.21 (B) (3)
ARE CLASS 2 REMOTE - CONTROL cables permitted to be
STRAPPED or otherwise attached to RACEWAYS for support ?
,3 | Page
A) No, this is prohibited
B) Yes, if the raceway is supported properly according to the NEC
C) Yes, if the raceway is not flexible but rigid, such as rigid metal
conduit, electrical metallic tubing, etc.
D) Yes, if the raceway contains power supply conductors for equipment
which the class 2 circuit conductors control - CORRECT ANSWER-
No, this is prohibited
article 725.143
Where flexible cord is connected to the building ceiling with a suitable "
tension take - up device" the maximum length of the cord from the
supply joint to the take - up device is _____________ feet.
A) 4
B) 4
C) 6 D) 8 - CORRECT ANSWER 63
, 4 | Page
article 368.56 (B) (2)
All of the following WIRING METHODS are permitted in a ceiling
space used as a return - air plenum except:
A) IMC
B) NMC
C) EMT
D) MI CABLE - CORRECT ANSWER-NMC
article 300.22 (B)
Excluding exceptions, nonmetallic sheathed cable is permitted in all of
the following areas EXECPT: - CORRECT ANSWER-Above a
suspended ceiling of a retail store
article 334.12 (A) (2)
The NEC permits 3/8 - inch FLEXIBLE METAL CONDUIT to be
unsupported for tap connection to light fixtures, provided the length
doses not exceed __________ feet. - CORRECT ANSWER-6