What is the minimum clearance to the edge of a wood stud for a wire hole? -ANSWERS-1 1/4
inches(NEC 300.4 A 1)
What is the minimum separation between a class 1 fire alarm circuit conductor and a class 2 or
class 3 circuit? -ANSWERS-1/4 inch
A basic alarm system will have __ power sources. -ANSWERS-2
What is the minimum required clearance between a receiving antenna and 250 volt line not
insulated? -ANSWERS-2 Feet
The minimum clearance for an antenna to other conductors is? -ANSWERS-2 Feet (NEC 810.13)
How far away must communications cables be from electric, light, or power conductors -
ANSWERS-2 inches
what is the maximum blink rate on a strobe light per second? -ANSWERS-2 (NFPA 72 18.5.2.1)
On a voice alarm system what is the minimum number of cycles it has to report an evacuation
procedure? -ANSWERS-2 (NFPA 72 24.4.1.2.1)
What is the minimum required height for a propriety manual pull fire alarm? -ANSWERS-3 1/2
feet or 42 inches
, An overhead feeder must have a clearance of __ from chimneys, radio, and television antennas.
-ANSWERS-3 Feet (NEC 225.19 B)
The NEC classifies Continuous Load as equipment running at a maximum load of __ ____? -
ANSWERS-3 hours
A continuous load is a load where the maximum current is expected to continue for a certain
length of time. This amount of time is? -ANSWERS-3 hours or more
The minimum head room of working space above service equipment, switchboards, panel
boards, or motor control centers shall be at least: -ANSWERS-6.5 feet
What is the minimum required separation between communication cables and lighting
conductors? -ANSWERS-6 feet
What is the minimum separation required between coaxial cable in a CATV system and lighting
conductors -ANSWERS-6 feet
On a radio antenna receiving station what is the minimum clearance between lead-in
conductors and conductors forming a part of a lightning protection system? -ANSWERS-6 feet
What is the minimum length of a grounding rod in an application of less than 50 volts? -
ANSWERS-8 Feet (NEC 250.5.2.5)
Utility owned low-voltage communication, radio, and television coaxial cables may pass directly
over a pool if at a minimum height of: -ANSWERS-10 feet