CONTENTS ANSWERED CHECKED
AUTHENTIC 2026 GRADED A+
⩥ Wiring methods and materials permitted in Class I, Division 1
locations include _____.
Answer: All of These
- threaded rigid metal or threaded steel IMC
- flexible fittings listed for Class I, Division 1 locations
- boxes approved for Class I, Division 1 locations
(501.10 (A))
⩥ Type PVC conduit, Type RTRC conduit, and Type HDPE conduit
shall be permitted in Class I, Division 1 underground locations where
encased in a concrete envelope a minimum of _____ in. thick and
provided with not less than _____ in. of cover measured from the top of
the conduit to grade.
Answer: 2, 24
(501.10 (A)(1)(1) Exception)
,⩥ MI cable terminated with fittings listed for the location is allowed in
Class I, Division 1 locations. (True or False)
Answer: True
(501.10 (A)(1)(2))
⩥ In industrial establishments with restricted public access where only
qualified persons will service the installation, MC-HL cable is allowed
to be used in a Class I, Division 1 location if it _____ and terminated
with fittings listed for the application. Such cable shall comply with Part
II of Article 330.
Answer: All of These
- is listed for use in Class I, Zone 1, or Division 1 locations
- has a gas/vaportight continuous corrugated metallic sheath, an overall
jacket of suitable polymeric material
- has a separate equipment grounding conductor(s) in accordance with
250.122
(501.10 (A)(1)(3))
⩥ When necessary to employ flexible connections in a Class I, Division
1 location, such as at motor terminals, flexible fittings listed for the
location or flexible cord in accordance with 501.140, are permitted if
terminated with cord connectors listed for the location. (True or False)
Answer: True
, (501.10 (A)(2)(2))
⩥ When necessary to employ flexible connections in a Class I, Division
1 location, such as at motor terminals, _____ shall be permitted.
Answer: Any of These
- flexible fittings listed for the location
- flexible cord in accordance with the provisions of 501.140, terminated
with cord connectors listed for the location
- listed Type TC-ER-HL in industrial establishments with restricted
public access, where the conditions of maintenance and supervision
ensure that only qualified persons service the installation, and installed
in accordance with 336.10
(501.10 (2))
⩥ Wiring methods permitted in Class I, Division 1 locations are
permitted in Class I, Division 2 locations. (True or False)
Answer: True
(501.10 (B)(1))
⩥ _____ is(are) among the wiring methods permitted within a Class I,
Division 2 location.