A fire alarm system with a pre-signal feature installed on the protected premises shall be pre-
permitted if ✔Correct Answer-Approved by the AHJ
A pressure supervisory signal-initiating device for a dry-pipe sprinkler system shall indicate
✔Correct Answer-Both high and low pressure conditions
A seperate storage battery and separate automatic charger shall be provided for straight the
engine-driven generator and shall ✔Correct Answer-Not be used for any other purpose
The secondary power supply for in building mass notification system shall be capable of
operating the system during emergency conditions for ______________________ and shall be
capable of operating the system during emergency conditions for ____________________ at
minimum connected load ✔Correct Answer-24 hrs/ 15 mins
All fire alarm systems shall test free of ______________________ ✔Correct Answer-Grounds
The alarm audible signal pattern used to notify building occupants of the need to evacuate shall
be the standard alarm evacuation signal consisting of a(n) ✔Correct Answer-Three pulses
temporal pattern
If guards are used to protecting a notification appliance such as strop eight it shall ✔Correct
Answer-Be listed to be used with the appliance
Maintenance of household fire alarm systems be conducted ✔Correct Answer-According to
the manufacturer's instructions
Battery chargers shall be tested ✔Correct Answer-Annually
According to the NFPA 72 line type heat detectors shall be located on the ceiling or on the
sidewalls not more than ✔Correct Answer-20 in from the ceiling 30 inches from the sidewall
A signal transmits several discrete bits of informatio0n is a ✔Correct Answer-Code signal
Testing personnel shall have knowledge and experience acceptable to ✔Correct Answer-The
AHJ
Who shall be notified before testing of the fire alarm system? ✔Correct Answer-All building
occupants and personnel
The monitoring company