with 400 Practice Questions and Correct Answers
2026 / Journeyman Electrician License Latest
Practice Test Bank (New!)
Questions 1–25 (Multiple Choice)
1. What is the minimum bending radius for non-shielded power cables rated
over 1000 volts?
A. 4 times the cable diameter
B. 6 times the cable diameter
C. 8 times the cable diameter
D. 12 times the cable diameter
Answer: C
Rationale: NEC 300.34: For conductors over 1000V, minimum bending radius
is 8 times the cable diameter for non-shielded, 12 times for shielded.
2. A 120-volt, 15-ampere general purpose branch circuit in a dwelling unit can
supply how many VA maximum?
A. 1,440 VA
B. 1,500 VA
C. 1,800 VA
D. 2,000 VA
Answer: C
Rationale: 120V × 15A = 1,800 VA.
3. The ampacity of 8 AWG THHN copper conductor at 90°C is?
A. 40 A
B. 45 A
C. 50 A
D. 55 A
,Answer: D
Rationale: NEC Table 310.16: 8 AWG THHN copper at 90°C = 55 amps.
4. A 240-volt, 4,800-watt water heater draws how many amperes?
A. 10 A
B. 15 A
C. 20 A
D. 30 A
Answer: C
Rationale: Amps = Watts / Volts = 4, = 20 A.
5. What is the minimum burial depth for direct burial cable (UF) under a
residential driveway?
A. 6 inches
B. 12 inches
C. 18 inches
D. 24 inches
Answer: D
Rationale: NEC Table 300.5: UF cable under driveway (subject to vehicle
traffic) requires 24 inches.
6. The maximum number of 12 AWG THHN conductors permitted in trade
size 1-inch EMT is?
A. 12
B. 14
C. 16
D. 18
Answer: C
Rationale: NEC Annex C, Table C.1: 1" EMT with 12 AWG THHN = 16
conductors.
7. According to NEC 210.8(A), GFCI protection is required for all 15A and
20A, 125V receptacles in a dwelling unit bathroom. This applies to
receptacles within how many feet of a sink?
,A. 3 ft
B. 4 ft
C. 6 ft
D. All bathroom receptacles regardless of distance
Answer: D
Rationale: NEC 210.8(A)(1) requires GFCI protection for all bathroom
receptacles, not distance-based.
8. A 30-ampere, 240-volt dryer receptacle must be protected by a circuit
breaker with a rating of?
A. 15A
B. 20A
C. 30A
D. 40A
Answer: C
Rationale: NEC 210.21(B)(1): Overcurrent device rating shall not exceed the
receptacle rating (30A).
9. The minimum size equipment grounding conductor (EGC) for a 50-
ampere circuit is?
A. 14 AWG
B. 12 AWG
C. 10 AWG
D. 8 AWG
Answer: C
Rationale: NEC Table 250.122: 50A circuit requires 10 AWG copper EGC.
10. A 5-horsepower, 230-volt, single-phase motor has a full-load current
(FLC) of approximately?
A. 20 A
B. 28 A
C. 34 A
D. 40 A
, Answer: B
Rationale: NEC Table 430.248: 5 HP, 230V, single-phase = 28 A FLC.
11. The minimum size copper conductor for a 30-ampere motor circuit (non-
continuous) is?
A. 14 AWG
B. 12 AWG
C. 10 AWG
D. 8 AWG
Answer: C
Rationale: NEC 240.4(D): 30A requires 10 AWG copper minimum.
12. What is the minimum working space width in front of a 480V electrical
panel?
A. 24 inches
B. 30 inches
C. 36 inches
D. 48 inches
Answer: B
Rationale: NEC 110.26(A)(2): Minimum width is 30 inches or width of
equipment, whichever is greater.
13. A 120-volt, 1,440-watt space heater draws ____ amperes.
A. 10 A
B. 12 A
C. 14 A
D. 16 A
Answer: B
Rationale: 1, = 12 A.
14. The maximum number of 14 AWG THHN conductors in a trade size 1/2-
inch EMT is?
A. 6
B. 8