During an operational test of a foam water sprinkler system, if the nozzles are plugged what
color tag is used?
Red
Steel water storage tanks without corrosive protection are to be inspected how often?
3 Years
A sprinkler head with a white frame has a temperature rating of?
175 - 225°F
The weekly test of a Diesel fire pump is how long?
30 minutes
The weekly test of an electric fire pump is how long?
10 minutes
,Upon inspection of a sprinkler system, if the hydraulic nameplate is missing what color tag is
used?
Yellow
When inspecting a preaction system, if the electrical components are not in service what color
tag is used?
Red
Vane type water flow devices shall be tested how often?
Semi-annually
Proper number of spare heads and wrenches shall be inspected how often?
Annually
The temperature rating of a sprinkler head with a green glass bulb is?
175 - 225°F
When inspecting a sprinkler system if the spare sprinkler cabinet is missing what color tag
should be used?
Yellow
,On a dry pipe sprinkler head if no tests were conducted in 12 years what color tag should be
used?
Orange
Red Tag
Impairment (Notify FDNY, shall be fixed immediately)
Orange Tag
Critical Deficiency (Notify FDNY if not fixed after 30 days)
Yellow Tag
Non-critical Deficiency (Notify FNDY if not fixed after 30 days)
Green Tag
System fully operational without defects
How often shall the stem of an OS&Y Valve be lubricated
Annually
The 3 year dry pipe trip test is to be performed by whom?
, MP & MFSPC
Fire department connections are to be inspected how often?
Quarterly
Water motor gongs are to be tested how often?
Quarterly
In a water spray fixed system inspection if the strainer is found corroded what color tag is
required?
Yellow
A sprinkler head with a red frame has a temperature classification of?
Extra High (325 - 375°F)
The Hydraulic name plate shall be inspected how often?
Quarterly
What color tag is required when sprinkler heads are found to be lightly corroded?
Orange