Determine the MINIMUM trade size electrical metallic tubing (EMT)
required to enclose eight (8) size 6 AWG copper conductors with
THHW insulation, when installed in a 50 foot conduit run?
1 1/4 in.
Where exceptions are not applicable, when a feeder supplies a
continuous load of 240 amperes, the overcurrent protection
device protecting this
circuit shall have a rating of at LEAST ?
300 amperes
Liquidtight flexible metal conduit (LFMC) shall be securely fastened
WITHIN
_____ of each box or other conduit termination?
12 inches
,Where a pull box to be installed will contain conductors of size 4
AWG and larger, and a straight pull of the conductors is to be made,
the length of the box shall NOT be less than ____times the trade
diameter of the largest
conduit entering the box.
eight
Conduit nipples not over 24 inches in length may be filled to a
MAXIMUM of of their cross-sectional area.
60 percent
Determine the MAXIMUM number of size 14 AWG THHN conductors
permitted to be installed in a trade size 3/8 in. flexible metal conduit
(FMC) that contains a bare size 14 AWG grounding conductor,
when the FMC has external fittings.
four
Which one of the following listed conduits does the NEC® permit to
enclose conductors supplying wet-niche underwater pool
luminaires?
Schedule 40 rigid polyvinyl chloride conduit (PVC)
, Underground wiring is not permitted under a permanently installed
swimming pool or within _____ of the pool, unless the wiring is
supplying the associated pool equipment.
5 feet
Which of the following listed types of batteries is NOT permitted
for use as a source of power for emergency systems?
automotive
In regard to electric space heating equipment, heating cables shall be
furnished complete with factory-assembled nonheating leads at
LEAST _____ in length.
7 feet
In guest rooms of hotels, motels, and sleeping rooms of dorms a
MINIMUM of _____ general purpose receptacles installed in the room
is/are required to be readily accessible.
two
A listed _____ shall be installed in or on all emergency systems
switchboards and panelboards?
surge protective device (SPD)