NYC MASTER ELECTRICIAN EXAM QUESTIONS AND ANSWERS /. Type ____ is multiconductor cable identified for use as underground service entrance cable. - Answer-Type USE cable /.Knife switch rated for more than 1200 Amps at 250Volts or less - Answer-Can be used only as isolating switch, shall not be opened under load /.Track lighting with outlets in a bathroom is not allowed because ? - Answer-Track lighting has receptacle /.Where internal combustion engines are used as the prime motor, an on site fuel supply shall be provided with an on premise fuel supply sufficient for not less than ____ hours full demand operation of the system - Answer-6 hours /.Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over ____ amperes shall be permitted to be supplied through a suitable attachment plug cap and hard service cable cord. - Answer-30 Amps /.Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - Answer-Both ends /.GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the ____type. - Answer-Locking /.The maximum voltage drop from service point to the last over-current device in a dwelling unit? - Answer-4% /.Which of the following statements best describe the grounding requirement for central vacuum outlet - Answer-Accessible non current carrying metal parts are required to be connected to an equipment grounding conductor. /.In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by at least two branch circuits, which ____permitted to originate from two separate transfer switches on the emergency system - Answer-Are permitted /.Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges ,day rooms, or similar areas - Answer-Do not include /.The patient care area is any portion of the healthcare facility where patients are intended to be ____or ____. - Answer-Examined or treated /.Each general care area patient bed location in a healthcare facility must be provided with four ____ or ____ duplex receptacles - Answer-Single or two /.A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical, care on a 24 hour basis of ____ or more patients - Answer-Four /.Where installed to reduce electrical noise for electronic equipment, electrical continuity of the metal raceways shall not be required and metal raceway can terminate a (an) ____ nonmetallic fitting or spacer on electronic equipment - Answer-Listed fitting /.Feeder and branch circuit conductors within ____ inches of a Ballast shall have an insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaiere marked as suitable for a different insulation temperature - Answer-3 inches /.Manufactured wiring systems constructed with type MC cable shall be supported and secured at intervals not exceeding ____ ft. - Answer-6 ft /.Where a main bonding jumper or a system bonding jumper is a screw only the screw shall be identified with a ____ that shall be visible with the screw installed - Answer-Green finish /.Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the window, cap, or other prominent part to distinguish them from fuses of higher ampere rating - Answer-Hexagon /.The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts (volt-amperes) or the nameplate rating, which ever is larger, for each dryer served ? - Answer-5000 watts /.Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of ____ windows that are designed to be opened, doors, porches, stairs fire escape or similar locations. - Answer-3 ft (36 inches) /.—— Cartridge fuses of the renewable type shall be permitted to be used only for replacement in existing installation is where there is no evidence of over-fusing or tampering. - Answer-Class H /.Branch circuit conductors within ____inches of the ballast shall have an insulation temperature rating not lower it 90°C 194°F - Answer-3" inches /.The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - Answer-8 /.In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground plug ? - Answer-Combination range hood/microwave oven /.Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent device up to the equipment ____ the type 3 SPD connection must be a minimum 30'ft of conductor a distance from the service or separately derived system disconnect - Answer-Included in the manufactures instructions /.Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ? - Answer-EVJ /.Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be removed - Answer-Type S fuse /.Service drops Installed over roof shall have a vertical clearance of ____ above the roof surface, and unless a lesser distance is permitted by and exceptions - Answer-8'ft /.Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with conductors of Class 1 or electric light or power conductors, unless ____. - Answer-Separated by barrier /.In the critical care areas of health care centers, each patient bed shall be provided with a minimum of ____ duplex receptacles - Answer-3 duplex (6 single) /.The equipment system shall supply major electric ____ necessary for patient care and basic hospital operation - Answer-Equipment /.The essential electrical system in a healthcare facility shall be compromised of the - Answer-emergency system and the: equipment system /.Locations were flammable anesthetics are employed are class I,Division I locations that shall extend - Answer-upwards to a level 5'ft above the floor /.In a healthcare facility receptacles and attachment plugs in a hazardous (classified) location with an anesthizing area shall be listed for use in class I group ____ locations - Answer-Group C /.In anesthetic,areas health care equipment frequently in contact with bodies of persons shall not exceed ____ volts. - Answer-10 Volts /.In anesthetic areas, low-voltage equipment that is frequently in contact with the bodies of persons or has exposed current-carrying elements shall - Answer-operate on an electrical potential of 10 volts or less,be moistur- resistant, be approved as intrinsically safe or double-insulated equipment. /.In a healthcare facility, the maximum internal current permitted to flow through a line isolated monitor,when any point of the isolated system is grounded, shall be ____ . - Answer-1 milliamperes

Show more Read less
Institution
NYC MASTER ELECTRICIAN
Course
NYC MASTER ELECTRICIAN

Content preview

NYC MASTER ELECTRICIAN EXAM
QUESTIONS AND ANSWERS

/. Type ____ is multiconductor cable identified for use as underground service entrance
cable. - Answer-✅Type USE cable

/.Knife switch rated for more than 1200 Amps at 250Volts or less - Answer-✅Can be
used only as isolating switch, shall not be opened under load

/.Track lighting with outlets in a bathroom is not allowed because ? - Answer-✅Track
lighting has receptacle

/.Where internal combustion engines are used as the prime motor, an on site fuel supply
shall be provided with an on premise fuel supply sufficient for not less than ____ hours
full demand operation of the system - Answer-✅6 hours

/.Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over
____ amperes shall be permitted to be supplied through a suitable attachment plug cap
and hard service cable cord. - Answer-✅30 Amps

/.Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - Answer-
✅Both ends

/.GFCI protection at a carnival is not required for equipment at circuit if the receptacle is
of the ____type. - Answer-✅Locking

/.The maximum voltage drop from service point to the last over-current device in a
dwelling unit? - Answer-✅4%

/.Which of the following statements best describe the grounding requirement for central
vacuum outlet - Answer-✅Accessible non current carrying metal parts are required to be
connected to an equipment grounding conductor.

/.In healthcare facilities, patient bed receptacles located in general care areas shall be
supplied by at least two branch circuits, which ____permitted to originate from two
separate transfer switches on the emergency system - Answer-✅Are permitted

/.Patient care areas of healthcare facilities ____ areas such as business offices,
corridors, lounges ,day rooms, or similar areas - Answer-✅Do not include

/.The patient care area is any portion of the healthcare facility where patients are
intended to be ____or ____. - Answer-✅Examined or treated

,/.Each general care area patient bed location in a healthcare facility must be provided
with four ____ or ____ duplex receptacles - Answer-✅Single or two

/.A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or
surgical, care on a 24 hour basis of ____ or more patients - Answer-✅Four

/.Where installed to reduce electrical noise for electronic equipment, electrical continuity
of the metal raceways shall not be required and metal raceway can terminate a (an)
____ nonmetallic fitting or spacer on electronic equipment - Answer-✅Listed fitting

/.Feeder and branch circuit conductors within ____ inches of a Ballast shall have an
insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaiere
marked as suitable for a different insulation temperature - Answer-✅3 inches

/.Manufactured wiring systems constructed with type MC cable shall be supported and
secured at intervals not exceeding ____ ft. - Answer-✅6 ft

/.Where a main bonding jumper or a system bonding jumper is a screw only the screw
shall be identified with a ____ that shall be visible with the screw installed - Answer-
✅Green finish

/.Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of
the window, cap, or other prominent part to distinguish them from fuses of higher
ampere rating - Answer-✅Hexagon

/.The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____
watts (volt-amperes) or the nameplate rating, which ever is larger, for each dryer served
? - Answer-✅5000 watts

/.Service conductors installed as unjacketed multiconductor cable shall have a minimum
clearance of ____ windows that are designed to be opened, doors, porches, stairs fire
escape or similar locations. - Answer-✅3 ft (36 inches)

/.—— Cartridge fuses of the renewable type shall be permitted to be used only for
replacement in existing installation is where there is no evidence of over-fusing or
tampering. - Answer-✅Class H

/.Branch circuit conductors within ____inches of the ballast shall have an insulation
temperature rating not lower it 90°C 194°F - Answer-✅3" inches

/.The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - Answer-✅8

/.In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment
ground plug ? - Answer-✅Combination range hood/microwave oven

,/.Type 3 Surge Protective devices can be installed on the load side of a branch circuit
overcurrent device up to the equipment served.if ____ the type 3 SPD connection must
be a minimum 30'ft of conductor a distance from the service or separately derived
system disconnect - Answer-✅Included in the manufactures instructions

/.Which flexible cable is Allowed to be used for electric vehicle charging station 300
Volts ? - Answer-✅EVJ

/.Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that
cannot be removed - Answer-✅Type S fuse

/.Service drops Installed over roof shall have a vertical clearance of ____ above the roof
surface, and unless a lesser distance is permitted by and exceptions - Answer-✅8'ft

/.Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or
similar fittings with conductors of Class 1 or electric light or power conductors, unless
____. - Answer-✅Separated by barrier

/.In the critical care areas of health care centers, each patient bed shall be provided with
a minimum of ____ duplex receptacles - Answer-✅3 duplex (6 single)

/.The equipment system shall supply major electric ____ necessary for patient care and
basic hospital operation - Answer-✅Equipment

/.The essential electrical system in a healthcare facility shall be compromised of the -
Answer-✅emergency system and the: equipment system

/.Locations were flammable anesthetics are employed are class I,Division I locations
that shall extend - Answer-✅upwards to a level 5'ft above the floor

/.In a healthcare facility receptacles and attachment plugs in a hazardous (classified)
location with an anesthizing area shall be listed for use in class I group ____ locations -
Answer-✅Group C

/.In anesthetic,areas health care equipment frequently in contact with bodies of persons
shall not exceed ____ volts. - Answer-✅10 Volts

/.In anesthetic areas, low-voltage equipment that is frequently in contact with the bodies
of persons or has exposed current-carrying elements shall - Answer-✅operate on an
electrical potential of 10 volts or less,be moistur- resistant, be approved as intrinsically
safe or double-insulated equipment.

/.In a healthcare facility, the maximum internal current permitted to flow through a line
isolated monitor,when any point of the isolated system is grounded, shall be ____ . -
Answer-✅1 milliamperes

, /.Transfer eguipment, including automatic transfer switches,shall be - Answer-
✅automatic, identified for emergency use , approved by the authority having jurisdiction

/.Automatic transfer switches shall be ____ operated and ____ held - Answer-
✅Electrically operated and mechanically

/.Audible and visual signal devices for an emergency system shall be provided,where
practicable, for the purpose(s) of indicating that - Answer-✅the battery is carrying load,
derangement of emergency source, that the battery charger is not functioning

/.Wiring from an emergency source to emergency loads shall ____ ____ ____ ____ of
all other wiring - Answer-✅Be kept entirely independent of all other wiring

/.Emergency circuit wiring shall be permitted to enter which of the following types of
equipment with normal circuit wiring? - Answer-✅Transfer switches, exit or emergency
luminaries supplied from two sources

/.Emergency circuit wiring must be designed and located in such a manner so as to
minimize the possibility of failure because of ____, ____, ____. - Answer-
✅Vandalism,flood,fire.

/.Emergency lighting emergency power or both must be available in the building within a
time not exceeding ____seconds - Answer-✅10 seconds

/.A storage battery supplying emergency lighting and power shall maintain not less than
87.5% of full fault is that total low for a period of at least 1.5 hours - Answer-✅

/.Where an internal combustion engine is used as the prime mover for the emergency
system and on-site fuel supply shall be provided for not less than 6 hours of full-demand
operation of the system - Answer-✅

/.Unit equipment (battery packs) shall be on the same branch circuit as that serving the
normal lighting in the area and connected ahead of any local switches - Answer-✅

/.The alternate source for emergency systems shall not be required to have ground-fault
protection of equipment with automatic disconnecting means - Answer-✅

/.They equipment grounding terminal buses of the normal and essential branch-circuit
panelboards serving the same individual patient care vicinity shall be connected
together with an insulated continuous copper conductor not smaller than 10 AWG -
Answer-✅

/.Each patient bed location in critical care areas shall be supplied by at least 2 branch
circuits. - Answer-✅

Written for

Institution
NYC MASTER ELECTRICIAN
Course
NYC MASTER ELECTRICIAN

Document information

Uploaded on
May 27, 2026
Number of pages
37
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

$16.49
Get access to the full document:

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Brainariam Harvard University
Follow You need to be logged in order to follow users or courses
Sold
147
Member since
1 year
Number of followers
7
Documents
8374
Last sold
4 days ago

Our store offers a wide selection of materials on various subjects and difficulty levels, created by experienced teachers. We specialize on NURSING,WGU,ACLS USMLE,TNCC,PMHNP,ATI and other major courses, Updated Exam, Study Guides and Test banks. If you don't find any document you are looking for in this store contact us and we will fetch it for you in minutes, we love impressing our clients with our quality work and we are very punctual on deadlines. Please go through the sets description appropriately before any purchase and leave a review after purchasing so as to make sure our customers are 100% satisfied. I WISH YOU SUCCESS IN YOUR EDUCATION JOURNEY

Read more Read less
3.3

25 reviews

5
8
4
2
3
8
2
3
1
4

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions