all records - ANSWER ✔✔must be kept on site for 3 years
planned removal from service - ANSWER ✔✔When the system or
portion of standpipe system is placed out of service for inspection,
testing, maintenance, etc. , no more than one floor can be out of service
and notification must be made to impairment coordinator
Unplanned out of service condition: - ANSWER ✔✔A serious defect
in the standpipe or sprinkler system including, but not limited to: an
empty tank, a break or major leak in the system's water piping,
inoperative or shut water supply valves, defective fire department
, connections, construction related shut downs affecting more than one
floor, or complete or partial shut downs of the standpipe system, other
than a shut down for a planned removal from service.
notification for planned removal from service - ANSWER ✔✔no
notification to the fire department is required provided the system will
fully return to service within 8 hours
notification for unplanned removal from service - ANSWER
✔✔reporting to owner of building and to FDNY BOROUGH
DISPATCHER
red tag on standpipe - ANSWER ✔✔system full out of service or
partially
white disc on fire dep connection - ANSWER ✔✔system fully out of
service
blue disc on fire dep connection - ANSWER ✔✔system partially out
of service
Automatic Standpipe System - ANSWER ✔✔A standpipe system
that is attached to a water supply capable of supplying the system
demand at all times and that requires no action other than opening a
hose valve to provide water at hose connections.