THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS.
AND TO DETERMINE QUALIFICATIONS. - ANSWER ✔✔OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED
ON PREMISES FOR A MIN. OF __________ YEARS. - ANSWER
✔✔3
,THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO
COMPLY WITH REQUIREMENTS. - ANSWER ✔✔IMPAIRMENT
COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE. - ANSWER ✔✔1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. -
ANSWER ✔✔1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS. - ANSWER
✔✔8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________
AND THE FIRE DEPT. - ANSWER ✔✔OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED
WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN
IMPAIRMENT. - ANSWER ✔✔30
,WHAT DOES "OOS" STAND FOR? - ANSWER ✔✔OUT OF
SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT
FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE
COMMAND CENTER - ANSWER ✔✔TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES. - ANSWER ✔✔MASTER
FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH
STATIC AND FLOW PRESSURES BEFORE AND AFTER. -
ANSWER ✔✔DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - ANSWER ✔✔NO
IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. -
ANSWER ✔✔MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE. -
ANSWER ✔✔RED
COPYRIGHT©PROFFKERRYMARTIN 2025/2026. YEAR PUBLISHED 2026. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE.
PRIVACY STATEMENT. ALL RIGHTS RESERVED
, A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE. - ANSWER ✔✔WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF
SERVICE. - ANSWER ✔✔BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS. - ANSWER
✔✔INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED. - ANSWER ✔✔IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL
NOT GREATHER THAN ________ PERCENT SHALL BE USED TO
PROTECT FROM FREEZING. - ANSWER ✔✔50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________. - ANSWER ✔✔MAIN
CONTROL VALVE