Exam Questions and Answers |
Already Graded A+
Sprinkler System - ANSWER ✔✔A fire extinguishing system, other
than a water mist system, that utilizes water as the extinguishing agent.
Automatic/Non-Automatic Sprinkler Systems - ANSWER ✔✔Shall be
inspected by a competent person holding a S12 CoF and employed or
contracted by the owner, to see that all parts of the system are in good
working order, and that the fire department connections, if any, are ready
for immediate use by the fire department.
,6 Extra Sprinkler Heads - ANSWER ✔✔A Supply of ____ shall be
kept available on the premises, to replace promptly any fused or
damaged_____
Fire Department Connections/Connections for a Sprinkler System -
ANSWER ✔✔Subjected to a hydrostatic pressure test to demonstrate
its suitability for fire department use, every 5 years.
Impairment Coordinator - ANSWER ✔✔Complies with the
requirements of study material
Impairment Coordinator - ANSWER ✔✔Shall take the actions when
a standpipe system, sprinkler system or the fire alarm system is out of
service.
Impairment Coordinator - ANSWER ✔✔Shall maintain records of all
system inspections, tests, servicing and other items of maintenance.
Impairment Coordinator - ANSWER ✔✔Building Owner in the
absence of a specific designee.
Planned Removal From Service - ANSWER ✔✔When the system, or
a portion of the sprinkler system, is placed out of service for a scheduled
inspection, testing, regular maintenance, minor repairs or for
construction affecting not more than 1 floor.
,Unplanned Out of Service Condition - ANSWER ✔✔A serious defect
in the sprinkler system including, but not limited to: an empty tank, a
break or major leak in the system's water piping, inoperative or shut
water supply valves, defective fire department connections, construction
related shut downs affecting more than one floor, or complete or partial
shut downs of the sprinkler system, other than a shut down for a planned
removal form service.
Tag Requirement - ANSWER ✔✔Shall be used to indicate that a
system, or portions are out of service.
Tags - ANSWER ✔✔Shall indicate the are affected, a brief
description of the condition, the occupancy classification, CoF number
and the estimated time until the system becomes operational.
Green Tags - ANSWER ✔✔If no impairment is found in the entire
system ___ will be placed on the main control valve.
Systems Fully Out of Service - ANSWER ✔✔White Discs 8-9" in
diameter is placed on all affected fire department connections. A red tag
shall be placed at the main control valve indicating the sprinkler
company name, date of removal from service and anticipated return to
service date.
COPYRIGHT©PROFFKERRYMARTIN 2025/2026. YEAR PUBLISHED 2026. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE.
PRIVACY STATEMENT. ALL RIGHTS RESERVED
, Systems Partially Out of Service - ANSWER ✔✔Blue Discs 8-9" in
diameter is placed on all affected fire department connections. a red tag
shall be placed at the main control valve and ay closed sectional valve
indicating the company name, date or removal from service and
anticipated return to service date.
Fire Watch - ANSWER ✔✔Building staff trained and knowledgeable
in conducting a fire watch may conduct a ____ in lieu of a fire guard
during the initial 4 hours of a planned removal from service, or after
discovery of an unplanned out-of-service condition, provided that the
floor or area in which the fire protection system is out of service does not
exceed 50,000 sqft.
CoF Holder - ANSWER ✔✔Responsibilities include: Record
Keeping, Records, Detailed Records, Riser Card Updates.
Record Keeping - ANSWER ✔✔Maintain a detailed record of all
inspections.
Records - ANSWER ✔✔All system inspections, tests, servicing and
other maintenance required by this NYC Fire Code, the NYC Fire rules
or the referenced standards shall be maintained on the premises for a
minimum of 3 years.