SET QUESTIONS AND ANSWERS SURE A+
✔✔Preliminary, bid, approval, construction, as-built - ✔✔Drawings have different stages
which are?
✔✔Request for proposal (RFP) - ✔✔Oftentimes a project will begin with a _________.
✔✔•certified value specialist
•owner's representatives
•designers and consultants
•the construction team
•cost estimator
•building management staff
•third-party (independent) reviewers - ✔✔Value-engineering team typically consist of?
✔✔•Information gathering
•brainstorming
•analysis
•development
•recommendations - ✔✔Value-engineering typically goes through phases which are?
✔✔Planning stage - ✔✔At what stage does value-engineering provide the most benefit?
, ✔✔Value = Function / Cost - ✔✔Value-engineering equation is:
✔✔Low cost and high value - ✔✔Value-engineering cost vs value goal is?
✔✔Giving careful consideration to all options, without sacrificing the project's goals. -
✔✔Value-engineering of a project involves:
✔✔Request for Information (RFI) - ✔✔Discrepancies between the plans and
specifications should be resolved using a?
✔✔36 inches - ✔✔Minimum distance between the deflector and the top of the storage
shall be?
✔✔8 foot on center - ✔✔The minimum distance control modes sprinklers can be spaced
apart is?
✔✔12 inches - ✔✔The minimum distance an upright control mode sprinkler shall be
permitted to be offset horizontally from the pipe is?
✔✔12 inches - ✔✔The minimum distance upright control mode sprinkler shall be
located above the centerline of the pipe for pipe greater than 4 inch nominal in
diameter?
✔✔8 foot - ✔✔The minimum distance ESFR sprinklers can be spaced apart is?
✔✔12 sprinklers located on 3 branch lines - ✔✔How many sprinklers are required to be
calculated on ESFR systems?
✔✔Preventing flashover in the room of origin where sprinklered; thereby allowing
occupants to escape - ✔✔The goal of NFPA 13D and NFPA 13R is?
✔✔400 square foot - ✔✔Pipe or tube listed for light hazard occupancies is permitted in
ordinary hazard rooms otherwise light hazard occupancies where the room does not
exceed _________. This allows the uses of nonmetallic pipe in small rooms such as
closets and mechanical rooms.
✔✔•lobbies not in hotels and motels
•foyers
•corridors
•halls
•lounges
•ordinary hazard areas (per NFPA 13R section 7.2.4.1)
•garages (per NFPA 13R section 7.3.3 and 7.3.3.1(1)