EXAM LATEST QUESTIONS AND ANSWERS SURE
A+
✔✔•wet
•in locations where the piping may freeze - ✔✔Class I standpipe systems shall be
_______ systems, unless installed....?
✔✔•automatic wet
•automatic dry
•semiautomatic dry
•They are to be installed in a location where piping is subject to freezing
•A fire brigade is trained to operate the system without fire department intervention -
✔✔Class II and Class III standpipe systems shall be _________ _____ systems. They
are permitted to be ___________ _______ or __________ _______ systems, under the
following circumstances:
✔✔•The FLOOR level of the highest story is located MORE than 30 feet above the
lowest level of fire department vehicle access.
•The FLOOR level of the lowest story is located MORE than 30 feet below the highest
level of fire department vehicle access. - ✔✔Class III standpipe systems shall be
installed throughout buildings, if ONE of the following two conditions exists:
, ✔✔•75
•the lowest level of fire department vehicle access - ✔✔NPFA defines a high-rise
building as a building where the floor of an occupiable story is greater than _______
feet above...:
✔✔•I
•an automatic sprinkler system in accordance with installation requirements contained
within the IBC. - ✔✔Class ______ standpipes are allowed in buildings equipped
throughout with?
✔✔•I manual
•150 feet above the lowest level of fire department vehicle access - ✔✔Class _______
_________ standpipes are allowed in open parking garages where the highest floor is
located not more than....?
✔✔•I manual dry
•hose connections are located as required for Class II standpipes in accordance with
location of Class II standpipe hose connection requirements - ✔✔Class _______
_________ _______ standpipes are allowed in open parking garages that are subject to
freezing temperatures, if the....?
✔✔•I
•basements
•automatic sprinkler system - ✔✔Class ________ standpipes are allowed in
____________ equipped throughout with an ________ _________ _________.
✔✔•I
•automatic wet
•non-sprinklered
•1000 - ✔✔Class _________ __________ ___________ standpipes shall be provided
in ______________ Group A buildings have an occupant load exceeding __________
persons.
✔✔•I
•automatic dry
•semiautomatic dry
•manual wet
•high-rise - ✔✔Class ________ _________ _________ and __________ __________
standpipes or _________ _________ standpipes are allowed in building that are not
___________ buildings.
✔✔Class I hose connections connected to the automatic sprinkler system sized to
deliver water at 250gpm at the most hydraulically remote hose connection while