ACTUAL ALL QUESTIONS AND ANSWERS SURE A+
✔✔Information signs should indicate which of the following? - ✔✔Location if the area
served by system, the presence and location of antifreeze or other auxiliary systems,
the presence and location of heat tape
✔✔Which of the following signs require a quarterly inspection to verify that it is securely
attached to the sprinkler riser? - ✔✔Hydraulic Design Information sign
✔✔Which of the following would be an acceptable material for the information sign to be
made of? - ✔✔Rigid plastic/ Metal
✔✔How often shall the system information sign be tested? - ✔✔Testing is not required
for the information sign
✔✔Sprinklers shall be tested for sensitivity and functionality at ______ PSI - ✔✔5
✔✔What specialized equipment is needed to test waterflow alarm devices on a wet pipe
system? - ✔✔None
, ✔✔Sprinklers subject to overspray accumulation shall be protected by using? - ✔✔A
thin paper bag
✔✔What type of testing requires the use of a refractometer? - ✔✔Antifreeze System
✔✔What type of device is used to test flow rates? - ✔✔Pilot Gauge
✔✔Identify what type of sprinkler is designed to be installed in such a way that the
water stream is directed downward against the deflector? - ✔✔Pendent sprinkler
✔✔A class 1 standpipe system is a system that provides ________ hose connections to
water supply used by fire departments. - ✔✔2 1/2 in
✔✔What type of precautions should shall take place prior to entering confined spaces
such as tanks, valve pits, or trenches? - ✔✔Legally required
✔✔All penetrations into the area of cold storage shall be inspected. If an ice obstruction
is found during the inspection, what requirement shall be employed? - ✔✔Additional
pipe shall be examined to ensure no ice blockage exists.
✔✔Internal examination of sprinkler pipe shall be performed at what areas while
conducting an obstruction investigation and prevention? - ✔✔Systems valve, riser, and
cross main
✔✔NFPA 25 chapter 15 outlines the procedure to follow for impairment of a water
based system. Besides this code requirement other action shall be followed based on
the impairment? - ✔✔Attachment of a tag
✔✔Normally closed valves shall be secured by the means of a seal or , be ________ in
accordance with the applicable NFPA standard. - ✔✔Electrically supervised
✔✔What is the frequency for testing the hose connections for pressure reducing and
relief valves? - ✔✔60 Months
✔✔In systems where the sole water supply is through a backflow preventer and/ or
pressure reducing valves, the main drain test of at least one system downstream of the
device shall be conducted ________? - ✔✔Quarterly
✔✔Hose connections should be inspected, tested, and maintained in accordance with
NFPA 25 Chapter ______ and Chapter____? - ✔✔6,13
✔✔When is the proper time for the employee's to receive training on the company fall
arrest system? - ✔✔Before using the fall arrest system