⩥ The continuity of the grounded conductor shall depend on a
busbar or __ only.
Continuity, Grounded conductors
200.12.
Answer: wire.
⩥ Each multi-wire branch circuit shall be provided with a means
that will ____ disconnect all ungrounded conductors at the point
where the branch circuit originates.
Disconnecting means, Branch circuits, multiwire 210.4(B).
Answer: Simultaneously
⩥ Balconies, decks, and porches that are accessible from the
inside of the dwelling unit shall have at least one receptacle not
more than __ ft. above the balcony, deck, or porch surface.
,Balconies, outdoor, receptacles for,
210.52(E)(3).
Answer: 6 1/2
⩥ Where it is impracticable to locate the service head above the
point of attachment, the service head location shall be permitted
not farther than ___ inches from the point of attachment.
Service drops, Connections, service head
230.54 (C) Exception.
Answer: 24
⩥ True/False: One of the means by which grounding conductors
and bonding jumpers shall NOT be connected by is machine
screw type fasteners.
Connection of Grounding and Bonding Equipment 250.8.
Answer: False
⩥ Cables with entirely nonmetallic sheaths are permitted to
enter the top of a surface-mounted enclosure through one or
more nonflexible raceways not less than 450 mm (18 in.) and
not more than __ feet in length
, Cabinets, Cutout Boxes, and Meter Socket Enclosures. 312.5(C).
Answer: 10
⩥ The maximum allowable overcurrent protection for four 14/2
NM cables installed in contact with thermal insulation without
maintaining spacing between cables is:
Nonmetallic-sheathed cable, Insulation, Ampacity,
334.112, 334.80.
Answer: 15
⩥ What kind of protection is required for an outdoor receptacle
located under the soffit of a dwelling for holiday lighting?
Ground-fault circuit interrupters, Outdoors, dwelling units,
210.8(A)(3).
Answer: GFCI