FINAL EXAM 2026 GRADED A+
Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over ____
amperes shall be permitted to be supplied through a suitable attachment plug cap and hard
service cable cord. - ANSWER --30 Amps
Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - ANSWER --
Both ends
GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the
____type. - ANSWER --Locking
Type ____ is multiconductor cable identified for use as underground service entrance cable. -
ANSWER --Type USE cable
Knife switch rated for more than 1200 Amps at 250Volts or less - ANSWER --Can be used
only as isolating switch, shall not be opened under load
Track lighting with outlets in a bathroom is not allowed because ? - ANSWER --Track
lighting has receptacle
Where internal combustion engines are used as the prime motor, an on site fuel supply shall be
provided with an on premise fuel supply sufficient for not less than ____ hours full demand
operation of the system - ANSWER --6 hours
,The maximum voltage drop from service point to the last over-current device in a dwelling unit?
- ANSWER --4%
Which of the following statements best describe the grounding requirement for central vacuum
outlet - ANSWER --Accessible non current carrying metal parts are required to be
connected to an equipment grounding conductor.
Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the
window, cap, or other prominent part to distinguish them from fuses of higher ampere rating -
ANSWER --Hexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts
(volt-amperes) or the nameplate rating, which ever is larger, for each dryer served ? -
ANSWER --5000 watts
Service conductors installed as unjacketed multiconductor cable shall have a minimum
clearance of ____ windows that are designed to be opened, doors, porches, stairs fire escape or
similar locations. - ANSWER --3 ft (36 inches)
—— Cartridge fuses of the renewable type shall be permitted to be used only for replacement
in existing installation is where there is no evidence of over-fusing or tampering. -
ANSWER --Class H
Branch circuit conductors within ____inches of the ballast shall have an insulation temperature
rating not lower it 90°C 194°F - ANSWER --3" inches
The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - ANSWER --8
, In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground
plug ? - ANSWER --Combination range hood/microwave oven
Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent
device up to the equipment served.if ____ the type 3 SPD connection must be a minimum 30'ft
of conductor a distance from the service or separately derived system disconnect -
ANSWER --Included in the manufactures instructions
Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ? -
ANSWER --EVJ
Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be
removed - ANSWER --Type S fuse
In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by
at least two branch circuits, which ____permitted to originate from two separate transfer
switches on the emergency system - ANSWER --Are permitted
Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges
,day rooms, or similar areas - ANSWER --Do not include
The patient care area is any portion of the healthcare facility where patients are intended to be
____or ____. - ANSWER --Examined or treated
Each general care area patient bed location in a healthcare facility must be provided with four
____ or ____ duplex receptacles - ANSWER --Single or two
A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical,
care on a 24 hour basis of ____ or more patients - ANSWER --Four