of 2026 containing verified & solved questions and answers
with back-up rationales
Question 1
A commercial building has a water-based fire protection system. A sprinkler head shows signs of
corrosion during an annual inspection. Who is responsible for correcting this deficiency?
A) The local fire department
B) The insurance carrier
C) The property owner or designated representative
D) The sprinkler manufacturer
-CORRECT ANSWER- The property owner or designated representative
Rationale: The property owner or designated representative shall correct or repair
deficiencies or impairments found during inspection, testing, and maintenance.
Question 2
During a monthly inspection of a dry pipe system, you notice the air gauge near the compressor
reads 40 psi but the gauge near the dry pipe valve reads 35 psi. What action is required?
A) Add more air to the system immediately
B) The air line shall be taken out of service
C) Replace both gauges with new ones
D) Document the difference and continue normal operations
-CORRECT ANSWER- The air line shall be taken out of service
Rationale: When the gauge near the compressor reads higher than the gauge near the
dry pipe valve, the air line shall be taken out of service.
Question 3
A facility has 800 sprinklers installed. How many spare sprinklers must be kept on site according
to the standard?
A) 6
B) 12
C) 24
D) 36
-CORRECT ANSWER- 12
Rationale: For protected facilities having 300 to 1000 sprinklers, no fewer than 12 spare
sprinklers are required.
Question 4
You are inspecting sprinklers in a manufacturing area that is inaccessible for safety
considerations due to ongoing process operations. When must these sprinklers be inspected?
A) Annually from floor level
B) Never, they are exempt
C) During each scheduled shutdown
D) Monthly using a lift device
-CORRECT ANSWER- During each scheduled shutdown
Rationale: Sprinklers in areas inaccessible for safety considerations due to process
operations shall be inspected during each scheduled shutdown.
,Question 5
A property owner has just completed testing of auxiliary drain and test valves, including
reinstalling plugs and caps. What additional action is required?
A) Notify the insurance company
B) Shall be restored to full operational condition
C) Replace all gaskets within 30 days
D) Submit a written report to the local fire marshal
-CORRECT ANSWER- Shall be restored to full operational condition
Rationale: After testing and reinstallation of plugs and caps for auxiliary drain and test
valves, they shall be restored to full operational condition.
Question 6
An electric motor-driven fire pump must be operated automatically and run for what minimum
duration?
A) 5 minutes
B) 10 minutes
C) 15 minutes
D) 30 minutes
-CORRECT ANSWER- 10 minutes
Rationale: The electric pump shall run a minimum of 10 minutes when operated
automatically.
Question 7
A facility has a diesel engine-driven fire pump. How often must this pump be operated?
A) Monthly
B) Semi-annually
C) Weekly
D) Annually
-CORRECT ANSWER- Weekly
Rationale: Diesel engine-driven fire pumps shall be operated weekly.
Question 8
During a main drain test, you observe a 12% reduction in full flow pressure compared to the
previous test. What must be done?
A) No action needed if reduction is under 15%
B) Replace the main drain valve immediately
C) The cause of the reduction shall be identified and corrected
D) Increase the water supply pressure by 15%
-CORRECT ANSWER- The cause of the reduction shall be identified and corrected
Rationale: When there is a 10 percent reduction in full flow pressure compared to original
or previous tests, the cause shall be identified and corrected.
Question 9
Sprinklers that have been in service for 50 years must be subjected to which action?
A) Tested at 5 year intervals
B) Inspected from floor level only
C) Replaced
D) Cleaned and recoated
,-CORRECT ANSWER- Replaced
Rationale: Where sprinklers have been in service for 50 years, they shall be replaced.
Question 10
A dry sprinkler has been in service for 10 years. What is required by the standard?
A) Replacement with a new dry sprinkler
B) Tested
C) Lubrication of the sealing surface
D) Inspection from floor level only
-CORRECT ANSWER- Tested
Rationale: Dry sprinklers that have been in service for 10 years shall be tested.
Question 11
Who is qualified to perform corrections and repairs on a water-based fire protection system?
A) Any licensed electrician
B) The property owner regardless of experience
C) Qualified maintenance personnel or a qualified contractor
D) The local fire inspector
-CORRECT ANSWER- Qualified maintenance personnel or a qualified contractor
Rationale: Qualified maintenance personnel or a qualified contractor are qualified to
perform corrections and repairs.
Question 12
A property owner wants to avoid false alarms while testing a sprinkler system that has
supervisory service. Who must be notified before conducting the test?
A) The insurance company only
B) The alarm receiving facility by the property owner or designated representative
C) The local police department
D) The sprinkler manufacturer
-CORRECT ANSWER- The alarm receiving facility by the property owner or designated
representative
Rationale: To avoid false alarms where supervisory service is provided, the alarm
receiving facility shall be notified before conducting any test that could result in alarm
activation.
Question 13
How often must sprinklers be inspected from the floor level?
A) Monthly
B) Quarterly
C) Semi-annually
D) Annually
-CORRECT ANSWER- Annually
Rationale: Sprinklers shall be inspected from the floor level annually.
Question 14
A facility has a wet pipe sprinkler system. How often must the gauges be inspected?
A) Weekly
B) Monthly
C) Quarterly
, D) Annually
-CORRECT ANSWER- Monthly
Rationale: Gauges on a wet pipe sprinkler system shall be inspected monthly.
Question 15
A building has a dry pipe sprinkler system. How often must the gauges be inspected?
A) Weekly
B) Monthly
C) Quarterly
D) Annually
-CORRECT ANSWER- Monthly
Rationale: Gauges on a dry pipe system shall be inspected monthly.
Question 16
Sprinkler pipe hangers and seismic bracing must be inspected from the floor level at what
frequency?
A) Monthly
B) Quarterly
C) Semi-annually
D) Annually
-CORRECT ANSWER- Annually
Rationale: Sprinkler pipe hangers and seismic bracing shall be inspected annually from
the floor level.
Question 17
Waterflow alarm and supervisory alarm devices must be inspected at which interval?
A) Monthly
B) Quarterly
C) Semi-annually
D) Annually
-CORRECT ANSWER- Quarterly
Rationale: Waterflow alarm and supervisory alarm devices shall be inspected quarterly.
Question 18
A mechanical waterflow alarm device such as a water motor gong must be tested how often?
A) Monthly
B) Quarterly
C) Semi-annually
D) Annually
-CORRECT ANSWER- Quarterly
Rationale: Mechanical waterflow alarm devices including water motor gongs shall be
tested quarterly.
Question 19
A vane-type waterflow alarm device must be tested at which frequency?
A) Monthly
B) Quarterly
C) Semi-annually
D) Annually