Failure to remove conduit burrs usually results in ______.
=ANSWER=Ground Faults
Where non-power-limited wiring is installed exposed, it
must be mechanically protected within ______ of the
finished floor. =ANSWER=7'
Which cable type is permitted to be installed exposed in a
plenum space? =ANSWER=FPLP
, Which of the following documents can assist in
determining if an assembly is two-hour rated?
=ANSWER=UL Fire Resistance Directory
Where run vertically, Annex A of NFPA 72 recommends a
separation of one foot for the outgoing and return
conductors of ______ circuits. =ANSWER=Class A, N, & X
Which article of the NEC covers burglary system wiring?
=ANSWER=Article 725
Fire alarm circuit conductors above a suspended ceiling
may use the same support wires that support the ceiling
grid. =ANSWER=False