Sprinklers segment 5, S-12 CITYWIDE
SPRINKLER SYSTEMS TEST BANK
EXAM 2026 2027\UPSATED S12& S13
WITH COMPLETE QUESTIONS AND
CORRECT DETAILED
ANSWERS\VERIFIED 100%
ALREADY GRADED A+\LATEST
UPDATE
Question 1: According to NYC Building Code (BC 903.6), what color MUST be
applied to the control valve handles of a dedicated automatic sprinkler system?
A) Red
B) Yellow
C) Green
D) Orange
Correct ,,,answer,,,,: C) Green
Rationale: NYC requires immediate visual identification for responding fire units.
Green handles indicate a dedicated sprinkler system. Red is for standpipe handles,
yellow for combination systems, and orange indicates a critical deficiency tag .
,Question 2: Who is responsible to maintain the sprinkler system and determine
qualifications of personnel?
A) The Fire Safety Director
B) The Building Owner
C) The FDNY Commissioner
D) The Master Plumber
Correct ,,,answer,,,,: B) The Building Owner
Rationale: The building owner is legally responsible for maintaining the sprinkler
system and ensuring that all personnel working on the system are properly
qualified .
Question 3: Records of all inspections and maintenance shall be maintained on
premises for a minimum of how many years?
A) 1 year
B) 2 years
C) 3 years
D) 5 years
Correct ,,,answer,,,,: C) 3 years
Rationale: FDNY regulations require that all inspection, testing, and maintenance
records be kept on the premises for a minimum of three years for review by
authorities .
,Question 4: The building owner shall assign a(n) ____________ to comply with
impairment requirements.
A) Fire Guard
B) Impairment Coordinator
C) Safety Director
D) Building Manager
Correct ,,,answer,,,,: B) Impairment Coordinator
Rationale: The Impairment Coordinator is responsible for ensuring proper safety
precautions are taken when a fire protection system is placed out of service .
Question 5: Regular maintenance and minor repairs not affecting more than how
many floor(s) are considered planned removal from service?
A) 0 floors (no floors)
B) 1 floor
C) 2 floors
D) 3 floors
Correct ,,,answer,,,,: B) 1 floor
Rationale: Minor repairs affecting no more than one floor can be considered a
planned impairment. Shutdowns affecting more than one floor require additional
notification and precautions .
, Question 6: Shutdowns affecting more than _________ floor(s) are considered
unplanned out-of-service conditions.
A) 0
B) 1
C) 2
D) 3
Correct ,,,answer,,,,: B) 1
Rationale: Any shutdown that affects more than one floor is automatically
classified as an unplanned out-of-service condition requiring immediate FDNY
notification .
Question 7: Notification to FDNY is NOT required, provided the system is
returned to service within how many hours?
A) 2 hours
B) 4 hours
C) 8 hours
D) 12 hours
Correct ,,,answer,,,,: C) 8 hours
Rationale: If a system can be returned to service within 8 hours, FDNY
notification is not required. Beyond 8 hours, notification is mandatory .