Newest 2026 Questions and Correct Detailed Answers
Already Graded A+
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER
THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING.
CORRECT ANSWER-50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. CORRECT ANSWER-MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE
DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. CORRECT
ANSWER-RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. CORRECT ANSWER-REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: CORRECT ANSWER-REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
,THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. CORRECT ANSWER-OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. CORRECT ANSWER-3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. CORRECT ANSWER-IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. CORRECT
ANSWER-1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. CORRECT ANSWER-1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. CORRECT ANSWER-8
,FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT.
CORRECT ANSWER-OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________
DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. CORRECT ANSWER-30
WHAT DOES "OOS" STAND FOR? CORRECT ANSWER-OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER CORRECT
ANSWER-TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. CORRECT ANSWER-MASTER FIRE SUPPRESSION
PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. CORRECT ANSWER-DRAIN TEST RESULTS
, GREEN TAGS INDICATE THAT __________. CORRECT ANSWER-NO
IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. CORRECT ANSWER-
MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. CORRECT ANSWER-RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. CORRECT ANSWER-WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. CORRECT ANSWER-BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. CORRECT ANSWER-INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. CORRECT ANSWER-
IMPAIRMENT COORDINATOR