Manufactured wiring systems constructed with type MC
cable shall be supported and secured at intervals not
exceeding ____ ft. - ANSWERS-6 ft
Where a main bonding jumper or a system bonding jumper
is a screw only the screw shall be identified with a ____ that
shall be visible with the screw installed - ANSWERS-Green
finish
Plug fuses a 15 amperes and lower rating shall be identified
by a ____ configuration of the window, cap, or other
,prominent part to distinguish them from fuses of higher
ampere rating - ANSWERS-Hexagon
The load for household electric clothes dryer's in a dwelling
unit(s) shall be either ____ watts (volt-amperes) or the
nameplate rating, which ever is larger, for each dryer served
? - ANSWERS-5000 watts
Service conductors installed as unjacketed multiconductor
cable shall have a minimum clearance of ____ windows that
are designed to be opened, doors, porches, stairs fire escape
or similar locations. - ANSWERS-3 ft (36 inches)
—— Cartridge fuses of the renewable type shall be
permitted to be used only for replacement in existing
installation is where there is no evidence of over-fusing or
tampering. - ANSWERS-Class H
Branch circuit conductors within ____inches of the ballast
shall have an insulation temperature rating not lower it 90°C
194°F - ANSWERS-3" inches
The minimum radius of a field bend on trade size 1 "1/4
RMC is ____. - ANSWERS-8
,In a dwelling unit which appliance is allowed to have a
24"inch cord with Attachment ground plug ? - ANSWERS-
Combination range hood/microwave oven
Type 3 Surge Protective devices can be installed on the load
side of a branch circuit overcurrent device up to the
equipment served.if ____ the type 3 SPD connection must
be a minimum 30'ft of conductor a distance from the service
or separately derived system disconnect - ANSWERS-
Included in the manufactures instructions
Which flexible cable is Allowed to be used for electric
vehicle charging station 300 Volts ? - ANSWERS-EVJ
Type ____ fuse adapters shall be designed so that once
inserted in a fuse holder that cannot be removed -
ANSWERS-Type S fuse
Service drops Installed over roof shall have a vertical
clearance of ____ above the roof surface, and unless a lesser
distance is permitted by and exceptions - ANSWERS-8'ft
, Class 2 and Class 3 circuits shall not be placed in any
enclosure, raceway, cable, or similar fittings with conductors
of Class 1 or electric light or power conductors, unless ____.
- ANSWERS-Separated by barrier
In the critical care areas of health care centers, each patient
bed shall be provided with a minimum of ____ duplex
receptacles - ANSWERS-3 duplex (6 single)
The equipment system shall supply major electric ____
necessary for patient care and basic hospital operation -
ANSWERS-Equipment
The essential electrical system in a healthcare facility shall
be compromised of the - ANSWERS-emergency system and
the: equipment system
Locations were flammable anesthetics are employed are
class I,Division I locations that shall extend - ANSWERS-
upwards to a level 5'ft above the floor
In a healthcare facility receptacles and attachment plugs in a
hazardous (classified) location with an anesthizing area shall