1. A dynamometer is designed to _____. - Correct Answer: read pulling
force during a cable pull
2. A good place to find data for supporting cable in vertical conduit runs is
from _____. - Correct Answer: manufacturers' catalogs
3. A typical hand-crank wire puller, using 30 pounds of force, can pull up to
_____. - Correct Answer: 1,500 pounds
4. Conveyor sheaves and rollers are MOST likely to be used when pulling cable
in _____. - Correct Answer: cable trays
5. If the estimated pulling force is 900 lbs, the pulling rope should be rated for
_____. - Correct Answer: 3,600 lbs
, 6. In general, a cable pull into cable tray should occur in a continuous
operation and at a rate of _____. - Correct Answer: 20 to 25 feet per
minute
7. In general, the allowable tension on a basket grip should NOT exceed _____.
- Correct Answer: 1,000 lbs
8. One of the most common types of wire-pulling rope is _____. - Correct
Answer: nylon
9. The amount of force applied to a pull is determined by the _____. -
Correct Answer: number of wraps on the puller drum (capstan)
10.The best way to reduce sidewall loading is to _____. - Correct Answer:
increase the radius of the bend
11.The ends of 1,000 kcmil conductors can be trimmed using _____. -
Correct Answer: cable cutters
12.The MOST important tool for supervising a high-force cable pull is _____. -
Correct Answer: working communications equipment
13.The preferred method of checking conduit for obstructions before pulling
cable is _____. - Correct Answer: performing a test pull