When a branch circuit feeds both noncontinuous and
continuous loads, the circuit must be sized to
accommodate 100% of the noncontinuous load plus what
percent of the continuous load?
A) 110%
B) 115%
C) 120 %
D) 125% - Answer-D) 125%
Article. 210.20 (A)
What is the allowable Ampacity of a 600 MCM copper
conductor type TW?
A) 300 Amps
B) 350 Amps
C) 355 Amps
,2|Page
D) 400 Amps - Answer-B) 350 Amps
Table- 310.16
The name given to a system or circuit conductor that is
intentionally grounded is?
A) Grounding Conductor
B) Bonding Conductor
C) High-leg conductor
D) Grounded or neutral conductor - Answer-D) Grounded
or Neutral Conductor
Article 100 Definitions
The value of current, time, or both at which an adjustable
circuit breaker is set to trip is known as?
A) Inverse time
B) Ampacity
C) Automatic
,3|Page
D) Setting - Answer-D) Setting.
Art. 100 Defintions
The cross-sectional area of three or more THW
conductors in a conduit must not exceed what percent of
the cross-sectional area of the conduit?
A) 30%
B) 40%
C) 50%
D) 60% - Answer-B) 40 %
Chapter 9 Table 1
EMT must be supported within what distance from an
outlet box, junction box, device box, cabinet, conduit body
or other terminations?
A) 3 feet
B) 4 feet
, 4|Page
C) 5 feet
D) 6 feet - Answer-A) 3 feet
Article 358.30 (A)
The panels of switchboards must be made of?
A) Moisture resistant, noncombustible material
B) Raintight material
C) Impact-resistant material
D) Waterproof material - Answer-A) Moisture-resistant,
noncombustible material
Article 408.50
A metal pole supporting a light fixture shall have an
accessible handhole not less than ________ inches?
A) 2 X 6 inches
B) 3 X 4 inches
C) 2 X 4 inches