Type ____ is multiconductor cable identified for use as underground
service entrance cable. - ANSWER ✔✔Type USE cable
Knife switch rated for more than 1200 Amps at 250Volts or less -
ANSWER ✔✔Can be used only as isolating switch, shall not be
opened under load
Track lighting with outlets in a bathroom is not allowed because ? -
ANSWER ✔✔Track lighting has receptacle
,Where internal combustion engines are used as the prime motor, an on
site fuel supply shall be provided with an on premise fuel supply
sufficient for not less than ____ hours full demand operation of the
system - ANSWER ✔✔6 hours
Fixed in place X-ray equipment properly supplied by a branch circuit
rated at not over ____ amperes shall be permitted to be supplied
through a suitable attachment plug cap and hard service cable cord. -
ANSWER ✔✔30 Amps
Where skin effect exist the ferromagnetic envelope shall be bonded at
____. - ANSWER ✔✔Both ends
GFCI protection at a carnival is not required for equipment at circuit if the
receptacle is of the ____type. - ANSWER ✔✔Locking
The maximum voltage drop from service point to the last over-current
device in a dwelling unit? - ANSWER ✔✔4%
Which of the following statements best describe the grounding
requirement for central vacuum outlet - ANSWER ✔✔Accessible non
current carrying metal parts are required to be connected to an
equipment grounding conductor.
,In healthcare facilities, patient bed receptacles located in general care
areas shall be supplied by at least two branch circuits, which
____permitted to originate from two separate transfer switches on the
emergency system - ANSWER ✔✔Are permitted
Patient care areas of healthcare facilities ____ areas such as business
offices, corridors, lounges ,day rooms, or similar areas - ANSWER
✔✔Do not include
The patient care area is any portion of the healthcare facility where
patients are intended to be ____or ____. - ANSWER ✔✔Examined or
treated
Each general care area patient bed location in a healthcare facility must
be provided with four ____ or ____ duplex receptacles - ANSWER
✔✔Single or two
A hospital is a building or portion thereof used for medical,
psychiatric,obstetrical , or surgical, care on a 24 hour basis of ____ or
more patients - ANSWER ✔✔Four
Where installed to reduce electrical noise for electronic equipment,
electrical continuity of the metal raceways shall not be required and
COPYRIGHT©PROFFKERRYMARTIN 2025/2026. YEAR PUBLISHED 2026. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE.
PRIVACY STATEMENT. ALL RIGHTS RESERVED
, metal raceway can terminate a (an) ____ nonmetallic fitting or spacer on
electronic equipment - ANSWER ✔✔Listed fitting
Feeder and branch circuit conductors within ____ inches of a Ballast
shall have an insulation temperature rating not lower than 90°C (194°F)
unless supplying a luminaiere marked as suitable for a different
insulation temperature - ANSWER ✔✔3 inches
Manufactured wiring systems constructed with type MC cable shall be
supported and secured at intervals not exceeding ____ ft. - ANSWER
✔✔6 ft
Where a main bonding jumper or a system bonding jumper is a screw
only the screw shall be identified with a ____ that shall be visible with
the screw installed - ANSWER ✔✔Green finish
Plug fuses a 15 amperes and lower rating shall be identified by a ____
configuration of the window, cap, or other prominent part to distinguish
them from fuses of higher ampere rating - ANSWER ✔✔Hexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall
be either ____ watts (volt-amperes) or the nameplate rating, which ever
is larger, for each dryer served ? - ANSWER ✔✔5000 watts