, The minimum size equipment grounding conductor for a 4
100 ampere, 120/240 volt single phase underground
dwelling feeder whose ungrounded conductors have been
increased in size from 3 AWG copper to 1 AWG copper is
__ AWG copper
Ampacities, Grounding
250.122(B) Table 250.122 Table 8 Ch 9
The continuity of the grounded conductor shall depend on wire.
a busbar or __ only.
Continuity, Grounded conductors
200.12
Each multi-wire branch circuit shall be provided with a Simultaneously
means that will ____ disconnect all ungrounded
conductors at the point where the branch circuit originates.
Disconnecting means, Branch circuits, multiwire 210.4(B)
Balconies, decks, and porches that are accessible from the 6 1/2
inside of the dwelling unit shall have at least one
receptacle not more than __ ft. above the balcony, deck, or
porch surface.
Balconies, outdoor, receptacles for,
210.52(E)(3)
Where it is impracticable to locate the service head above 24
the point of attachment, the service head location shall be
permitted not farther than ___ inches from the point of
attachment.
Service drops, Connections, service head
230.54 (C) Exception
True/False: One of the means by which grounding False
conductors and bonding jumpers shall NOT be connected
by is machine screw type fasteners.
Connection of Grounding and Bonding Equipment 250.8
Cables with entirely nonmetallic sheaths are permitted to 10
enter the top of a surface-mounted enclosure through one
or more nonflexible raceways not less than 450 mm (18
in.) and not more than __ feet in length
Cabinets, Cutout Boxes, and Meter Socket Enclosures.
312.5(C)
The maximum allowable overcurrent protection for four 15
14/2 NM cables installed in contact with thermal insulation
without maintaining spacing between cables is:
Nonmetallic-sheathed cable, Insulation, Ampacity,
334.112, 334.80
What kind of protection is required for an outdoor GFCI
receptacle located under the soffit of a dwelling for holiday
lighting?
Ground-fault circuit interrupters, Outdoors, dwelling units,
210.8(A)(3)