Rate of Cooling: Want to cool 11,000 CFM of Air. V = 13.8. What is the rate of cooling? -
Answer 11,000/13.8 = 797.1 lb/min
Heat Transfer, Water: The flow through a hot water heat exchanger is 15 gpm, EWT is
160 and LWT is 140. What is Q? - Answer Q = (500)(15)(160-140) = 150,000 BTUH
Heat Transfer, Air: 2,000 CFM, EAT is 72, LAT is 55. What is Q? - Answer Q = (1.1)
(2,000)(72-55) = 37,400 BTUH
Infiltration: Building built in 1971, size is 100' x 250' with 12' ceiling heights. What is the
infiltration rate for summer and winter? - Answer Summer = ((100x250x12) x 1(From
Chart))/60 mins = 5,000 CFM
Winter = ((100x250x12) x 1.5 (From Chart))/60 mins = 7,500 CFM
Ventilation: New style beauty shop intended for 23 occupants. - Answer 23 ppl x 25
cfm/person (from chart) = 575 CFM
R & U Value For Wall: Use tables 2.5 for film, 2-3A for components, 2-4 for air space. -
Answer If R value is given per inch, multiply that by the component's thickness for your
R. If the R is for thickness listed, use that number. Add all numbers for R. U value = 1/R
Building Heat Loss: 1,400 sq ft wall, U value = 0.1, Indoor temp is 70, Outdoor temp is
0. - Answer Q = (0.1) x (1,400) x (70-0) = 9,800 BTUH
Outdoor Air Heat Loss: Infiltration rate of 4,000 CFM, Ventilation rate of 6,000 CFM,
Indoor temp = 70, Outdoor temp = 0. - Answer Q = (6,000)(1.1)(70-0) = 462,000 BTUH
Calculating TETD for Walls: 4" face brick + 2" insulation + 8" common brick. Total SF =
20,000. 4PM, Dark Color. - Answer 1. Find Group from wall components using chart (K)
2. Find weight/sf from chart (130)
3. Find U Value from chart (0.10)
4. TETD is value from chart using time of day, group, and color. (22)
5. (0.10)(20,000)(22) = 44,000 BTUH
Calculating TETD for Roofs: 1' Insulation+ 2" HW Concrete. 4pm, 0.04 U value, roof
size = 30,000 sf, Dark Color. - Answer 1. Find TETD in table using roof components
(81)
2. (0.04)(30,000)(81) = 97,200 BTUH
What ASHRAE Standard is 55 2013? - Answer Thermal Environmental Conditions
What ASHRAE Standard is 62.1? - Answer Ventilation for Accurate Indoor Air Quality