For hot work operation with citywide permit, the owner of the premises of the hot work
operation areas must be notified in writing by the citywide permit holder ______ the hot
work is to be started.
at least 48 hours before
The pre-hot work check must be conducted by the responsible person before hot work
is authorized and __________
least once per day.
The check reports must be kept at the work site during the work, made available for
inspection by a representative of the FDNY, and maintained on the premises for a
minimum of
48 hours after work is complete.
A pre-hot work check must be conducted at least
once per day
Hot work operations involving cutting or welding shall be conducted at least
35 feet from combustible materials and combustible waste
All other hot work operations shall be conducted at least
25 feet from combustible materials and combustible waste
Sprinkler system protection ____________while hot work is performed.
must not be shut off or impaired
When should a Fire watch be maintained
A fire watch must be maintained during any hot work operation.
What other duties should the Fire Watch have while on hot water operations.
The persons conducting a fire watch shall not have other duties.
Where hose lines are required, they shall be connected, charged and ready for
operation
At least one portable fire extinguisher with a minimum 2-A:20-B:C
How far away should one fire extinguisher be from any operation
30 feet
The fire watch for torch operations conducted at the following three locations shall be
conducted by at least one F-60 fire guard
(1)Construction sites.
(2)In any building or structure, when the torch operation is conducted by a person
holding a citywide permit for torch operations.
(3)On any rooftop, or in connection with any torch-applied roofing system operation.
e not less than one multi-purpose portable fire extinguisher with a minimum
______________ for roofing operations utilizing heat-producing systems or other
ignition sources.
3-A 40-B:C
For any CNG or LPG torch operation, the first inspection shall be conducted when?
30 minutes after completion of torch operations; the second inspection 1 hour after
completion of torch operations.
The fire guards or fire watch personnel must complete a signed inspection report (or the
log book). This report must be submitted to and retained by who?
the person in charge of the torch operations